SMARTZONE UPS USER MANUAL
64
Figure 49: Battery Setup Page 1 (3-Phase UPS)
Press the left or right arrow on the “Battery Group” line to select 1 to 8 for the number of
EBP units connected to the UPS. The default value is 1 EBP.
The Boost/Float Conversion feature is a battery life optimization tool. Batteries age at
different rates, causing an imbalance in the batteries. Panduit recommends boosting
charge unbalanced batteries on a regular basis to extend the life of the battery.
By default, this feature is disabled (set to 0 months) on a new system with new
batteries. Panduit recommends enabling this feature 6 months after the battery has
been installed. Select the appropriate number for this value (1-24) based on the Cell
Float Voltage setting. Increase the frequency of this setting (set this number to a lower
month value) for a lower cell float voltage. (For a cell float voltage of 2.20, 2.21 or
2.22V, set this number to 3 months.) Decrease the frequency of this setting (set this
number to a higher month value) for a higher cell float voltage. (For a cell float voltage
of 2.28 or 2.29V, set this number to 6 months.) Use the following table for
recommended Boost/Float Conversion settings.
Float charging voltage
Recommended
Setting
(Month)
2.20 2.21 2.22 2.23 2.24 2.25 2.26 2.27 2.28 2.29
3
4
5
6
The Cell Float Voltage is a battery life optimization parameter. Press the left or right
arrows in the “Cell Float Volt (V/Cell)” line to adjust the battery cell float voltage from