SMARTZONE UPS USER MANUAL
65
2.20 to 2.29 V/cell in increments of 0.01V. The default value is 2.25 V/cell. A higher cell
float voltage will keep the batteries at a higher capacity but will have more impact on the
battery life.
Press the left/right arrows in the “Cell Boost Volt (V/Cell)” line to adjust the battery cell
boost voltage from 2.30 to 2.40 V/cell, the default value is 2.35 V/cell. A higher cell
boost voltage allows the battery to charge faster but will have more impact on the
battery life.
After making all the necessary changes on this page, press the “Save Config” button to
save the changes.
Press the down arrow to go to the next battery setup page. Press the up and over arrow
to return to the Advanced Setup Menu page.
Figure 50: Battery Setup Page 2 (3-Phase UPS)
Press the left/right arrows in the “Boost Charge Setting” line to enable or disable battery
boost charging. The default is Enable. This is a battery life optimization parameter.
Press the left/right arrows in the “No Battery Warning” line to enable or disable the
warning when a battery is not present. The default is Enable. When enabled, a warning
will trigger on the system when a battery is not detected by the UPS unit.
Press the left/right arrows in the “Shared Battery” line to enable or disable battery
charging through the parallel UPS units in the system. The default is Disable. Enabling
this feature allows the batteries to be charged from all the UPS units in the parallel