SMARTZONE UPS USER MANUAL
68
Press the left or right arrow on the “Bypass Volt Protect Upper Limit” line to adjust the
upper voltage limit from 5% to 25% with a default of +15% on 1-Phase UPS units, and
adjust the upper voltage limit from 10% to 20% with a default of +15% on the 3-Phase
UPS units.
Press the left or right arrow on the “Bypass Frequency Tracking Range” line to adjust
the frequency range from
±
1% to
±
10% with a default of
±
10%.
After making all the necessary changes on this page, press the “Save Config” button to
save the changes.
Press the up and over arrow to go to the Advanced Setting Menu page.
Dry Contact Setting Pages
These two pages allow the user to set the meaning of the internal input and output dry
contact ports on the 3-phase UPS units only. These pages are not available on the 5-
10kVA Single-Phase UPS units.
The first page allows the user to define the input dry contact points.
Figure 53: Dry Contact Setup Page 1 (3-Phase UPS)
Press the left or right arrow on the “IN 01” line to select the meaning (close, INV ON,
INV OFF, BATT Fault, Generator, User Alarm3, User Alarm4, Forbidden ECO, Force
INV OFF, Input Switch, Bypass Switch, BATT Switch, BATT Trip, BATT Ground,
Thunder, or EPO) of the first input dry contact (between IN pins 1 and 2 on the back of
the UPS). The default is Close. Close means there is nothing assigned to this input dry
contact. For example, if “INV ON” is assigned to this contact, then a remote closure of
this contact will cause the inverter to turn ON.