SMARTZONE UPS USER MANUAL
79
the “Stop Self-Check” button will immediately stop the battery test.
Note:
The UPS will run on battery while the battery test is in process. The total battery test
duration is 10 seconds.
Press the up and over arrow to return to the Common Menu page.
Fault Clear Page (10-20kVA 3-phase UPS only)
Press the Fault Clear button on the Common Menu page to manually clear certain UPS
faults. There are intermittent faults and self-recoverable faults that may be manually
cleared. Intermittent faults may occur based on erroneous readings. These faults may
randomly appear during certain external operating conditions. If the fault is intermittent,
it will get cleared through these steps. If the fault is persistent, the fault will reappear
after clearing. Some self-recoverable faults may frequently occur (10 times within one
hour) such as fan fault, rectifier overtemperature, rectifier overcurrent or frequent
switching to bypass. If the UPS switches to bypass 10 times within an hour it will lock
the UPS into the Bypass state. This fault must be cleared to enable the UPS to switch
back to the Normal state.
Figure 66: Fault Clear Page
Pressing on “Confirm” clears the faults on the system and then transitions the screen
back to the Common Menu page. Pressing “Cancel” returns the screen to the Common
Menu page without clearing the faults on the system.
About Pages
The About pages provide high-level information about the UPS and the firmware loaded
in the core modules of the UPS.