SMARTZONE UPS USER MANUAL
86
Fault
Code
Fault Description
Fault
Type
Buzzer
LED
Action to Take
operating temperature is at or
below 40°C
65
Battery Low
Temperature Alarm
Critical Continuous Red Alert
On
Ensure that the BAT-T cable is
properly connected between the
UPS and EBP
Ensure that the ambient
operating temperature is at or
above 0°C
66
Battery High
Temperature Alarm
Critical Continuous Red Alert
On
Ensure that the BAT-T cable is
properly connected between the
UPS and EBP
Ensure that the ambient
operating temperature is at or
below 40°C
67
Battery Temperature
Sensor Disconnected
Warning
Periodic
Yellow
Alert On
Ensure that the BAT-T cable is
properly connected between the
UPS and the first EBP
68
Fan Fault
Critical Continuous Red Alert
On
Remove ventilation obstructions
and reboot the UPS unit
69
UPS Over Temperature Critical Continuous Red Alert
On
Ensure that Ambient operating
temperature is at or below 40C.
Reduce the load
Check if the battery group is set
correctly
Remove ventilation obstructions
Reboot the UPS unit
70
Heatsink Over
Temperature Alarm
Critical Continuous Red Alert
On
Ensure that Ambient operating
temperature is at or below 40C
Reduce the load
Check if the battery group is set
correctly
Remove ventilation obstructions.
Reboot the UPS unit
71
Ambient High
Temperature Alarm
Warning
Periodic
Yellow
Alert On
Ensure that the ambient
operating temperature is at or