SMARTZONE UPS USER MANUAL
98
5
Buzzer beeps every
second and the
display shows “output
overload”.
The load on the output
of the UPS exceeds the
capability of the UPS.
Remove some load.
Use a higher kVA UPS for this
deployment.
6
The UPS only works
in bypass state.
The UPS is set to ECO
mode.
The transfer times to
Bypass state exceeded
the limit (10 x in an
hour).
Set the UPS working mode to
Normal Mode (non-parallel).
Reset the times of transferring to
bypass by clearing all the faults or
re-starting the UPS.
7
Cannot Cold start
Battery breaker is not
properly closed.
Battery is too low.
Battery quantity set
incorrectly.
Input breaker on the
rear panel not switched
ON.
Switch ON the battery breakers.
Recharge the battery and retry.
Power ON the UPS with AC to set
the battery quantity.
Switch ON the input breaker.
If the troubleshooting procedures do not solve the problem, contact Panduit Customer
Support at
or 1-800-777-3300 with the following information.
•
Product SKU and serial number.
•
Detailed explanation of the fault, such as LCD display info, LED lights status, etc.