SmartZone Gateway EP042 User Manual
-
28
-
3. Enter the IP address, subnet mask, and the Gateway that the SmartZone Gateway
unit will use (required). Contact your network administrator if you do not know the
values that you must enter here.
Note
: DHCP cannot be used for Rack Energy Kit Gateways. Select a Static
IP instead.
4. Enter the SNMP
System Name, System Location
, and
Contact Name
if
required. These fields will be added to all SNMP traps generated by the unit.
5. Click
Save
to confirm the changes.
6. Click
Restart
,and then select
Restart Now
to reboot the unit and implement the
changes.
Note
: Once the IP configuration has changed, the Gateway unit will no longer be access-
ible via the default IP address, because the new address will be operational.
7. The Gateway unit should now be connected to the main network and any further
required configuration will be done via the unit's new IP address.