SmartZone Gateway EPA064 User Manual
-
55
-
SNMP Only
This option allows only SNMP to command PDU outlets.
This effectively disables the Web Management Interface PDU outlet control.
RS232 Only
This option allows PDU control commands to be issued directly to a unit via the onboard
RS232 port. This option disables the Web Management Interface and SNMP control.
Cycle Up/Down Delay
This parameter specifies the interval in seconds between switching on and switching off
outlets when an entire PDU strip is cycled (all outlets commanded on or off).
Repeat Timer (on Comms Failure)
This parameter specifies the interval in seconds between when an initial PDU comms
failure trap is produced and a repeat trap is issued.
Reboot Delay
This parameter specifies how long (in seconds) an outlet remains off after a reboot
before switching back on.
Abort Cycle Delay
This parameter specifies how many seconds must elapse before a commanded cycle
begins on a PDU. This delay gives the user time to reverse the decision to cycle a PDU
before any outlet states are changed.
If you do not want to use this functionality, set the delay to zero.
Power – Configure Menu
When you click the
Config
button next to a device in the
Power/Configuration
tab, a
menu displays that allows you to specify all the available options for an individual
device.