Check the events log to see if all events have been wiped out
•
Check the Gateway EPA126 Panduit defaults are set (for example, System Name
value and sensor names, etc.).
Connectivity between Gateway EPA126 and PDU lost
–
Symptoms:
Not reporting power readings or power alarms reported on Gateway EPA126
–
Action:
•
Check if the connection between Gateway EPA126 and PDU via a RJ45 patch
cords has been disconnected
•
Check if the display panel driven by low-voltage supply from Gateway EPA126 is
enabled on the PDU
•
NOTE
: The Gateway EPA126 disconnection to the PDU does not affect the
power supply to PDU outlets. It only affects monitoring and control of power
outlets
How to audit Gateway EPA126 activities and changes
–
Symptoms:
A change is made to Gateway EPA126 or access to the container
–
Action:
•
Log into the Gateway EPA126 and click
the ‘Events’ link in the Setup screen
•
Review the events and timestamp to determine change or access logs
Power A and/or B Feed on Gateway EPA126 are disconnected/powered
down
–
Symptoms:
Gateway EPA126 lost power or is on single power feed