PDUs
Lost Comms
There are two basic reasons why you may see ‘Lost Comms’ messages from PDU ports.
1.
The PDU port is enabled, but does not have a PDU physically connected, in which case the port
can be disabled.
2.
The connection between the Gateway EPA126 PDU port and the PDU has become defective in
some way.
Resolution
1.
PDU Port Enabled but PDU not physically connected
In this situation, the unused PDU ports may be enabled, but not physically connected to a PDU.
Example: a cabinet may contain 2 PDU’s, but all 6 PDU
ports may be enabled in the Gateway
EPA126
, meaning that the 4 unconnected ports will generate ‘Lost Comms’ alerts.
A.
Point your browser at the IP address for the Gateway EPA126 to get to the Gateway EPA126
login page as follows:
B.
Login with the relevant credentials
C.
Navigate to the Power>Configure screen as shown below: