SMARTZONE G5 USER MANUAL
60
Sensor
Description
Sensor Measurement
Open/Close Door
Sends an alarm or
notification when a door on
which the sensor is
installed has been opened
more than 10 mm.
1
Rope Fluid Leak Sensor
Monitors for early detection
of liquid with a resistivity of
less than 2MOhms
(including distilled water) in
the monitored area. The kit
includes a 6m rope and
optional additional ropes
can be added with an
option.
1
Sensor Port Hub
Allows for up to three
environmental sensors to
be connected to the PDU.
N/A
Leak Detection Sensor
Extension
The kit includes one
additional 6m length rope
to pair with the leak
detection sensor. A total of
four extensions can be
added to the leak detection
sensor for a total length of
30m.
N/A
The optional environmental sensors can be installed before or after completing the PDU
installation, startup, and can be installed without turning off power to the PDU or the
devices connected. Panduit G5 Monitored, Switched, Monitored per Outlet, and
Monitored & Switched per Outlet PDUs are designed to collect a maximum of eight
environmental sensor measurements per PDU. For example, the Environmental 3-
Tempe 1-Humidity Sensor collects four sensor measurements. See the table
above for the sensor measurement collected from each environmental sensor.
All Panduit G5 PDUs have two physical sensor ports, and each PDU can collect a total
of eight sensor measurements (or readings). For example, if a PDU has an Open/Close
Door Sensor and an Environmental 3-Tempe 1-Humidity Sensor connected,
Summary of Contents for smartzone G5
Page 1: ...G5 PDU User Manual...
Page 11: ...SMARTZONE G5 USER MANUAL 10 Login Page Introduction to Web GUI...
Page 14: ...SMARTZONE G5 USER MANUAL 13 Environmental Page Security Page...
Page 35: ...SMARTZONE G5 USER MANUAL 34 Connect the RJ 45 end of the cable to the Serial RS485 1 connector...
Page 45: ...SMARTZONE G5 USER MANUAL 44...
Page 50: ...SMARTZONE G5 USER MANUAL 49 FOR 1 PHASE WITH BREAKERS FOR 3 PHASE WITH 6 BREAKERS...
Page 53: ...SMARTZONE G5 USER MANUAL 52 2 Select Outlet Control Enabled...
Page 55: ...SMARTZONE G5 USER MANUAL 54 5 Your Outlet Power Sequence has been set...
Page 59: ...SMARTZONE G5 USER MANUAL 58 9 RNA is now configured and enabled...