PVIQ™ CONNECTIVITY SYSTEM USER MANUAL V 1.0
85
turning both port LEDs green and two audio beeps (indicating both ends
are connected).
NOTE: If the panels at both ends of the connection were not placed into Learn mode
before the connections are made, you can recover by placing the second panel into
Learn mode after the connection was made.
NOTE: You may place all your panels into Learn mode before populating your cross-
connect patch field and the system will learn the connections as they are made.
However, any connection that was in place and was a security policy violation will
now be accepted as the security policy.
11. You may continue making additional patch connections between panels that are
in Learn mode.
a. When you make the first connection the LED above the port will light
amber and the system will provide a single audio beep.
b. When you make the second connection the LED above the port will light
amber and the system will provide a single audio beep, followed quickly by
turning both port LEDs green and two audio beeps (indicating both ends
are connected).
12. Change all panels in Learn mode back to secure mode. For each panel in Learn
mode, select
Secure
in the
Configuration Mode
field from the pulldown menu.
NOTE: You may have to log back into each system to change the panels back to
Secure Mode, because the web UI will automatically log you out after five minutes of
inactivity.
13. Click on the
Save
button to change the panel into Secure mode.
a. The Mode LED on the panel will extinguish.
14. Repeat steps 12 and 13 for each panel in Learn mode.
15. The new connection has been added to the system(s), and the panels are in
secure mode.
Removing a Cross-Connect Connection from the Patch Field
There are two methods to remove cross-connect cables from the patch field. The first
method is through individual port security policy clearing and the second method is
through panel Learn mode. The following sections provide the steps to implement either
method.