SMARTZONE G6 IRUPS USER MANUAL
43
Figure 57: Connect the EBP(s) - Example 4x EBP System
10-20kVA 3-Phase UPS and Associated EBP (U10N32V,
U10S32V, U15N32V, U15S32V, U20N32V, U20S32V, UVP480)
The 3-Phase systems may be configured as a Single System or as a Parallel System. In
addition, the output may be connected to single-phase loads or to 3-Phase loads.
Single Mode System Configuration with 3-Phase or Single-Phase
Output
All UPS units by default are configured as a single mode system. A single mode system
is a single UPS connected to an AC power source and that UPS provide the AC power
to the load.
This section provides the electrical connections for Single UPS with a 3-Phase input
and a 3-Phase or a Single-Phase Output.
•
When selecting, connecting, and routing power cables, follow local safety
regulations and rules.
•
If external conditions such as cable layout or ambient temperatures change, verifiy
in accordance with the IEC-60364-5-52 or local regulations.
1. Connect the UPS to the input source: