SMARTZONE G6 IRUPS USER MANUAL
54
together to ensure a proper connection.
151.
Replace the UPS faceplate.
152.
Change to Normal Mode.
EBP Battery Cartridge Sets for the 1-3kVA UPS Systems
(UVD024, UVD036, UVD048, UVD072)
Replace battery cartridges with only the same SKU. It is recommended to replace all
battery cartridges in a system at the same time with new battery cartridges of the same
SKU for that unit (UPS and EBP).
1. Change to Bypass Mode, this will not allow the UPS to transition to Battery Mode will
the battery cartridges are being replaced.
2. Remove the faceplate:
153.
Press both sides of EBP faceplate until the latches release and remove (see
Figure 65).
Figure 65: Press the Latches and Remove Faceplate
154.
Loosen the outer screws on both battery covers, move the battery covers to the
center, then pull the outside out (see Figure 66).