Page: 13 of 29 

2.2.11. RESET 

The UPS can be reset by using a standard #1 sized paper clip to depress the recessed Reset 
Button accessible from the bottom of the  unit.

  

With the power 

ON

, depress and hold the 

Reset Button.  Release the button after the LEDs  turn 

OFF

  and the LED initialization 

sequence begins. 
 

 

Figure 3: Reset Button Location 

 
 

2.2.12. RESTORE FACTORY DEFAULTS 

The user settable parameters can be restored to factory default values by using a standard #1 
sized paper clip to depress and hold the recessed reset button accessible from the bottom of 
the unit. Turn unit off. Depress the button and hold while switching the power on. Release the 
button  after  the LED turns off and the LED initialization sequence starts.  A list of the 
parameters and their factory default values are listed below. 
 

Item 

Description 

Default Values 

4.2.1.9   Charge Speed 

Slow 

 

Device Name 

Panduit UPS 

 

Network Settings  DHCP 

 

Password 

Serial number  

 

Username 

Panduit UPS 

 

Language 

English  

 
 
 
 
 

Summary of Contents for UPS003024024015

Page 1: ...ons TO REDUCE THE RISK OF INJURY USER MUST READ INSTRUCTION MANUAL Email techsupport panduit com EU Website www panduit com emea EU Email emeatoolservicecenter panduit com www panduit com Technical Su...

Page 2: ...nmental 3 Compliance 3 Installation 4 Performance 4 Indicators 5 User Interface 5 Network Interface 5 Maintenance 5 PRECAUTIONS AND GENERAL GUIDELINES 5 Safety Warnings 6 Electrical Safety Practices 6...

Page 3: ...WORK 22 4 6 CHARGE 24 4 7 SETTINGS 26 4 8 Table of Figures Figure 1 UPS 8 Figure 2 UPS Front Panel 9 Figure 3 Reset Button Location 13 Figure 4 DIN Rail Installation 15 Figure 5 System Block Diagram 1...

Page 4: ...ration 2G at 10 to 500 Hz Operational Shock 20G 11ms 3 bumps direction 18 bumps in total Compliance o FCC Title 47 CFR 15 Subpart B Emissions Class A o CAN ICES 3 A NMB 3 A ICES 003 Issue 5 o UL 1778...

Page 5: ...IEC 60529 The enclosure needs to only be accessible with the use of a tool Provision shall be made to prevent the rated voltage being exceeded by transient disturbances of more than 140 at the power...

Page 6: ...80 of original capacity 20 years at 20 C maximum UPS ambient 1 7 years at 40 C maximum UPS ambient 0 75 years at 60 C maximum UPS ambient NOTE Throughout this document the UPS003024024015 Uninterrupt...

Page 7: ...D THE USER S AUTHORITY TO OPERATE THE PRODUCT USE RECOMMENDED ACCESSORIES CONSULT THE OWNER S MANUAL FOR RECOMMENDED ACCESSORIES THE USE OF IMPROPER ACCESSORIES MAY CAUSE RISK OF INJURY TO PERSONS Ele...

Page 8: ...e personal protective equipment Safety glasses must be worn at all times by all persons installing the UPS Service Have your UPS serviced by a qualified repair person using only identical replacement...

Page 9: ...EDLC cells in series and the charge voltage is applied across all cells in the series or the stack of cells Due to small differences in cell capacitance and leakage current it is possible for one cell...

Page 10: ...INTERFACES OVERVIEW 2 1 The physical connections to the UPS are arranged on the top edge of the front panel of the unit which includes external sense resistor connections chassis ground and the input...

Page 11: ...upply line and the terminal marked is to be connected to the system ground The combined current draw of the UPS and the load shall not be any greater than 3 7A The operating input voltage range is 24...

Page 12: ...teady Off No Power If no power is supplied to the device the module status indicator shall be steady off Steady Green Device Operational If the device is operating correctly the module status indicato...

Page 13: ...only when all timed out Exclusive Owner connections arc reestablished Devices that support a single Exclusive Owner Connection shall transition to steady green when subsequent Exclusive Owner Connect...

Page 14: ...RY DEFAULTS The user settable parameters can be restored to factory default values by using a standard 1 sized paper clip to depress and hold the recessed reset button accessible from the bottom of th...

Page 15: ...reduced as the capacitors age however the minimum run time will be supported throughout the lifetime of the capacitors The estimated capacitor lifetime is based on the operating temperature of the ca...

Page 16: ...is required for proper operation of the device To install the UPS place the module with the DIN rail guide way on the top edge of the DIN rail and then snap it downwards and shown in Figure 4 To remov...

Page 17: ...h the provided optional load sense module The AC DC converter is connected to pin 3 of the current sense resistor while pin 4 is connected to the load Figure 5 shows the pin numbering of the current s...

Page 18: ...the load is retained The sense input and output terminals of the UPS are designed to accept UL CUL 12 to 30 AWG wire 12 gauge wires are recommended to reduce resistive losses and minimize error of the...

Page 19: ...ay be accomplished through EthernetIP communications EtherNet IP better known as the Common Industrial Protocol CIP was designed for use in process control and industrial automation applications CIP w...

Page 20: ...tp nnn nnn nnn nnn where nnn nnn nnn nnn is the IP address assigned to the UPS unit by the network USERNAME AND PASSWORD 4 3 When first accessing the Network Charge and Setting pages on the UPS or aft...

Page 21: ...has not been configured the module status indicator shall be flashing green Minor Fault If the device has detected a recoverable minor fault the module status indicator shall be flashing red NOTE An...

Page 22: ...e outside its enclosure 4 4 7 80 Capacity Years The estimated lifetime for the ELDC capacitors is 20 years for an operating temperature of 25 degrees Celsius or below The 80 Capacity parameter is init...

Page 23: ...l as when any of the bleed resistors are turned on or off A time stamp of the Elapsed Time is recorded with each of these events The Event Log can store a maximum of 1 000 events which are stored in s...

Page 24: ...cted that at least one of its IP addresses are already in use Self Test The device is performing its power on self test POST During POST the network status indicator shall alternate flashing green and...

Page 25: ...IP Address an optional Network Subnet Mask and optional Gateway address can also be entered The IP Address Mode can be restored to the factory default value as described in RESTORE FACTORY DEFAULTS S...

Page 26: ...le below shows the trade off between Charge Speed Charge Power and Charge Time Charge Speed Maximum Charge Power Approximate Charging Time Fast 53 Watts 10 minutes Medium 37 Watts 12 5 minutes Slow 20...

Page 27: ...efficiency of energy conversion and the current load power consumption The estimated hold time is calculated whether the UPS is in the charging or discharging state and is updated continuously as long...

Page 28: ...word 4 8 4 PASSWORD Clicking on the PASSWORD button allows the user access to change the default Password The new Password must be confirmed with a matching entry as shown below 4 8 5 FIRMWARE VERSION...

Page 29: ...ter performing a firmware updated the user should immediately perform a RESET 4 8 7 MAC ID The MAC ID Ethernet adapter device identifier is displayed The MAC ID is also printed on a label affixed to t...

Page 30: ...he WBI is displayed Clicking on the arrow displays a menu of available Languages Clicking on a different language followed by clicking on the SAVE button immediately to the right will change the Langu...

Reviews: