© Panduit Corp. 2018 

                 INSTALLATION INSTRUCTIONS 

Models:  VS-CKP14-6, VS-CKP4-000

 

T-PMPI-322EN 

Rev. 02 [10-2018] 

 

DOC#:  T-PMPI-322EN   

 

 

 

 

 

 

Page 

2

 of 

4

   

 

 

 

 

 

 

 

 

 

 

Rev 02 [10-2018]

 

Safety Information

 

This installation instructions contains information and warnings which must be followed to ensure safe 
termination and operation of the Insulation-piercing Connectors and an AVT Device. 

 

Always de-energize panel and verify absence of voltage in the panel before attempting to install 
connector.  Do not install connector on an energized conductor. 

• 

Installer must also follow all safety, installation, commissioning and operating steps from the 
AVT Device Manual.

 

• 

Connector is intended for one-time installation and use.  Do not reuse nor re-install connector.

 

Connection Kit Contents 

Connection Kits contain connectors and ferrules for installing an AVT Device, per below; 

CONNECTION 

KIT CATALOG 

PART NUMBER 

“RUN” Wire 

(CODE WIRE) 

“TAP” Wire AWG 

(Terminated w/ Ferrule) 

CONNECTOR 

FERRULE 

MIN. AWG 

[METRIC, mm2]

 

MAX. AWG 

[METRIC, mm2]

 

Catalog 

P/N 

Quantity 

Catalog 

P/N 

Quantity 

VS-CKP14-6 

14 AWG 

[2.1, r] 

6 AWG 

[13.3, r] 

14 AWG STR 

Class K 

(Terminated w/ Ferrule) 

VSC6 

F80-12-M 

12 

VS-CKP4-000 

4 AWG 

[21.2, r] 

3/0 AWG STR 

[85, r] 

VSC3/0 

F80-12-M 

12 

Step-by-Step Installation Procedure 

1.  See FIGURE 1:  Prepare (strip) AVT device sensor leads.

 

2.  See FIGURE 1:  Crimp ferrules F80-12-M onto sensor leads.

 

3.  See FIGURE 1:  Make locating mark on sensor leads.

 

 
 

 

4.  See FIGURE 2:  Review connector features.

 

5.  See FIGURE 2:  Loosen factory-tightened MAIN FASTENER

 

                           at least 6 full turns before proceeding to the next step.

 

 

                                                   

 

 

AFTER PROPER TERMINATION OF FERRULE, 
MARK LINE ON CONDUCTOR INSULATION 
FROM END OF CRIMPED FERRULE 

STRIP 
SENSOR LEAD 
INSULATION 

FERRULE F80-12-M 

0.875” 

FIGURE 1:  PREPARATION OF 
                    FERRULES ONTO 
                    SENSOR LEADS 

INSERTION PORTS FOR FULLY-INSERTED 
AND PROPERLY CRIMPED TAP WIRES 
(AVT SENSOR LEADS) INTO TERMINALS 
INSIDE THE CONNECTOR 

T10 TORX TERMINAL SCREWS ARE ACCESSIBLE 
FROM THE TWO PORTS AND ARE USED TO 
ADJUST TERMINALS INSIDE THE CONNECTOR.  
TERMINALS ARE USED TO SECURE A PAIR OF 
COLOR-CODED, FULLY-INSERTED AND 
PROPERLY-CRIMPED TAP WIRES (AVT SENSOR 
LEADS) WITHIN TERMINALS 

FIGURE 2:  CONNECTOR 
                    FEATURES 

MAIN FASTENER 