Figure 18: Fiber Enclosure Drawer showing the fiber cable when the drawer is closed.
40.
If a second Fiber Enclosure is required:
a.
Install the enclosure in RU21 indicated in
per FS002C, Opticom Rack Mount Fiber Enclosure
Installation Instructions.
b.
UPS Installation
41.
Install the UPS in RUs 2 and 3 indicated in the equipment elevation (
). Note that the horizontal bar on
the rear rail will support the UPS, eliminating excessive sag.
42.
Connect the ground cable to the UPS. It is Tak-Ty to the rear bottom support.
43.
Route the UPS power cord. Use the template on the bottom of the enclosure.
a.
Along the hinge
b.
Through the cord grip on the side of the enclosure
c.
Along the bottom front of the enclosure through the cord grips.
d.
Plug into the outlet box on the Lower Backplane.
e.
Use the Tak-Ty provided on the Backplane to retain the AC power Cord.
Copper Switch A&B Installation.
44.
Reference the Cisco Installation Instructions provided with the switches.