ALARMS

ON-BATTERY
When the UPS is operating on the batteries, the ON BATT LED will illuminate
and the audible alarm will sound once every ten-seconds.  The alarm will stop
once the UPS returns to the AC normal mode.

LOW BATTERY WARNING
When the batteries reach the pre-determined level the BATT LOW LED will
illuminate and the audible alarm will sound two beeps every five-seconds.  This
condition will continue until AC returns or the UPS shuts down from battery
exhaustion.

SELF TEST
The self test feature is useful to verify the correct operation of the UPS and the
condition of the batteries.  With the UPS in the AC normal mode, press the ON/
Test/Alarm Silencer Button for 1-beep (2-seconds) to perform a battery test.
The UPS will perform a ten-second self test.  During the self test, the UPS will
switch to battery power and the ON BATT LED will illuminate and the audible
alarm will sound.  If the UPS fails a self test, one of the LEDs will remain
illuminated indicating the type of problem.

UPS FAULT
When the UPS detects a hardware fault, the FAULT LED will illuminate and the
UPS will sound a constant alarm.  The fault condition, in some instances, may
be reset by turning the UPS off and then on again.

LOAD SHEDDING FUNCTION
The output receptacles are electrically wired into two segments to support the
"Load Shedding Function".  The user can control the two segments individually
or both at the same time.  The Load Shedding Function is controllable by the
Power Monitoring Software or the SNMP card.

OFF Button
Press the OFF button for 1-beep (2-seconds) to turn the UPS off.  NOTE:  The
input circuit breaker MUST be turned to the off position for the 208V models.

OUTPUT VOLTAGE SETTINGS
The inverter output voltage setting may be changed by the user to set the
desired Inverter output voltage.  The inverter output voltage setting can be either
120VAC (208VAC) default or 110VAC (240VAC).  The inverter output voltage
can be changed by using the Output voltage setting software.  The software
program is available for download on the web site.

OVERLOAD
When the amount of load attached to the UPS exceeds its power rating, the
OVERLOAD LED will illuminate and the UPS will sound a constant alarm.  This
alarm will remain on until the excess load is removed or the UPS’s self protec-
tion circuit shuts the UPS down.

COMMUNICATIONS PORTS (RS232 and USB)
The RS232 communication port is a standard DB9 female with both RS232 and
simulated contact closure capability.  The UPS will poll the port and activate
the port for RS232 or contact closure in accordance with the type of cable it
finds connected to the port.  To change the port configuration requires the unit
be turned off and restarted with the desired cable connected.  The pinout for the
port is depicted per the chart below:
Pin 1: Simulated contact closure Low Battery Warning, NO
Pin 2: /TXD
Pin 3: /RXD and receive UPS shutdown command (connect to pin9 for 4-sec-
onds.  The shutdown command is only active in the battery mode)
Pin 4: Not Used
Pin 5: Ground
Pin 6: Not Used
Pin 7: Not Used
Pin 8: Simulated contact closure AC fail, NO
Pin 9: Atx Signal (high level: 12V ± 2V, low level: -15V ± -2V)

WEAK/BAD BATTERY
The UPS automatically tests the battery’s condition and will illuminate the
REPLACE BATT LED and sound the alarm.  This alarm will be repeated until
the batteries pass a self test.  If the battery is weak or bad, the REPLACE
BATT LED will illuminate and the alarm will beep three times every five-minutes
until the battery is replaced.  It is recommended that the UPS be allowed to
charge overnight before performing a battery test to confirm a Weak/Bad Bat-
tery condition.
NOTE:  If the UPS has a REPLACE BATT Alarm after reconnecting or replacing
the batteries, the user must initiate a self test to clear the REPLACE BATT
Alarm.  To initiate a self test see section 4 "SELF TEST".

POWER MONITORING SOFTWARE
The UPS comes with a Power Monitoring Software CD.  See the software CD
for the installation of the Power Monitoring Software.

USB PORT
The USB protocol is HID.  The HID USB driver is standard in the Windows OS.
Simply plug the USB cable into the UPS and the computer then follow the
prompts on the screen.

OPTION SLOT
The option slot on the rear panel of the UPS is for option cards.  Contact your
local dealer for the available option cards.

RJ11 REPO (Remote Emergency Power Off) PORT
In the AC or the Battery mode short pin4 to pin5 for approximately 0.5-seconds
to shutdown the UPS.  The UPS must be turned off and then back on again to
restart the UPS.

Summary of Contents for ED1000RM2U

Page 1: ...User s Manual Endeavor Series Para Systems Inc 1455 Lemay Dr Carrollton TX 75007 Phone 1 972 446 7363 Fax 1 972 446 9011 Internet minutemanups com UPS Sizing sizemyups com PN 34000274 On Line UPS...

Page 2: ...d Indicators 6 3 Installation 9 4 Operation 15 5 Troubleshooting 18 6 Replacing the Battery 19 7 Obtaining Service 22 8 Specifications 23 9 Configurable Parameters Settings 25 10 Limited Product Warra...

Page 3: ...read this manual before installing your Endeavor On Line Series UPS models ED1000RM2U ED1000RMT2U ED1500RM2U ED1500RMT2U ED2000RM2U ED2000RMT2U ED3000RM2U ED3000RMT2U as it provides important informa...

Page 4: ...in are carefully designed to minimize any shipping damage In the unlikely case that the UPS needs to be returned to the manufacturer please use the original packing material Since the manufacturer is...

Page 5: ...ady state when the UPS reaches a low battery condition The BATT LOW LED is extinguished when the UPS is in the On Line mode and when the battery is not in a low battery condition The REPLACE BATT red...

Page 6: ...Receptacles ED1000RM2U NEMA 5 15P Model ED2000RM2U ED3000RM2U ED1500RM2U Input Power Plug All power cords are 10ft ED1000RMT2U ED1500RMT2U NEMA 5 15P NEMA 5 20P NEMA L5 30P NEMA 6 15P NEMA 6 15P 6 NEM...

Page 7: ...ARN ING Use two or more people when installing the UPS Use CAUTION the UPS is extremely heavy Do not move the rack after the units have been in stalled The rack maybe unstable due to the weight distri...

Page 8: ...lows the user to mount the UPS on the wall There is a wallmount bracket kit available for the UPS The kit includes two wall mounting brackets ten retaining screws and the wallmount template WARNING Us...

Page 9: ...Battery mode short pin4 to pin5 for approximately 0 5 seconds to shutdown the UPS The UPS must be turned off and then back on again to restart the UPS NOTE Connecting to the REPO port is optional The...

Page 10: ...will illuminate and the UPS will sound a constant alarm This alarm will remain on until the excess load is removed or the UPS s self protec tion circuit shuts the UPS down COMMUNICATIONS PORTS RS232 a...

Page 11: ...le Power Supply contains potentially hazardous voltages Do not attempt to disassemble the UPS beyond the battery replacement procedure This UPS contains no user serviceable parts Repairs and Battery r...

Page 12: ...12 LC R129 HR 1234W F2 8 Remove the two retaining screws for the battery retaining bracket FIG 3 9 Remove the battery retaining bracket FIG 3 10 Disconnect the Battery connectors red and black FIG 4...

Page 13: ...r a copy of your original sales receipt and a brief description of the problem 5 Mark the RMA on the outside of all packages The factory cannot accept any package without the RMA marked on the outside...

Page 14: ...e 15 to 45 C 5 to 113 F 24VDC 72VDC 2 12V8 5Ah 6 12V8 5Ah 15 5 13 4 60 dBA 24 0x17 3x3 5 610x440x89mm 39 4x23 6x9 0 1000x600x230mm 46 2 lbs 21 0 Kgs 55 0 lbs 24 7 Kgs 40 0 lbs 17 9 Kgs 29 0 lbs 13 2 K...

Page 15: ...r after delivery in regard to use or appli cation of Para Systems s equipment is furnished without charge and on the basis that it represents Para Systems s best judgment under the circumstances but i...

Page 16: ...ay Drive Carrollton Texas 75007 USA Type of Equipment Uninterruptible Power Supplies UPS Model No ED1000RM2U Y ED1500RM2U Y ED2000RM2U Y ED3000RM2U Y I hereby declare that the equipment specified abov...

Page 17: ...30 English Notes...

Reviews: