IF THE UPS REQUIRES SERVICE
1. Use the TROUBLESHOOTING section to eliminate obvious causes.
2. Verify there are no circuit breakers tripped. A tripped circuit breaker is the
most common problem.
3. Call your dealer for assistance. If you cannot reach your dealer, or if they
cannot resolve the problem call or fax MINUTEMAN Technical Support at
the following numbers; Voice phone (972) 446-7363, FAX line (972) 446-
9011 or visit our Web site at www.minutemanups.com the "Discussion
Board". Please have the following information available BEFORE calling
the Technical Support Department.
A. Your name and address.
B. Where and when the unit was purchased.
C. All of the model information about your UPS.
D. Any information on the failure, including LEDs that may be illuminated.
E. A description of the protected equipment, including model numbers if pos-
sible.
F. A technician will ask you for the above information and, if possible, help
solve your problem over the phone. In the event that the unit requires
factory service, the technician will issue you a Return Material Authoriza-
tion Number (RMA #).
G. If the UPS is under warranty, the repairs will be done at no charge. If not,
there will be a charge for repair.
4. Pack the UPS in its original packaging. If the original packaging is no longer
available, ask the Technical Support Technician about obtaining a new set.
It is important to pack the UPS properly in order to avoid damage in transit.
Never use Styrofoam beads for a packing material.
A. Include a letter with your name, address, day time phone number, RMA
number, a copy of your original sales receipt, and a brief description of the
problem.
5. Mark the RMA # on the outside of all packages. The factory cannot accept
any package without the RMA # marked on the outside.
6. Return the UPS by insured, prepaid carrier to:
Para Systems Inc.
MINUTEMAN UPS
1455 LeMay Drive
Carrollton, TX 75007
ATTN: RMA # _______
Default: 120VAC (208VAC), User selectable: 110VAC (240VAC)
1500VA/1200W
1000VA/800W
Protection
Waveform Type
Over-Current, Short-Circuit Protected and Latching Shutdown
True Sine Wave
Frequency
50/60Hz, +/-0.1Hz (unless synchronized to utility)
Nominal Voltage
Maximum Power Capacity
0 ms
>87% (Full Load)
Resettable Circuit Breaker
50 or 60 Hz, +/-6Hz, autosensing
0 - 150VAC (0 - 300VAC)
90 - 138VAC (160 - 280VAC)
120VAC: 117.6 - 122.4VAC (208VAC: 204 - 212VAC)
Transfer Time
Efficiency (Line Mode)
Input Protection
Frequency Limits
Voltage Range
Acceptable Input voltage
ED1500RM2U
ED1500RMT2U
ED1000RM2U
ED1000RMT2U
Model Number
SYSTEM SPECIFICATIONS
Voltage Range
Topology
Double Conversion On-Line, True Sine Wave
OUTPUT ON-LINE OPERATION
INPUT
Number of Phase
Single (1
∅
2W +G)
Nominal Voltage
120VAC (208VAC)
Low Voltage Transfer Point 80/90V (160V) resets to Utility Power at 86/96V (170V) or higher
High Voltage Transfer Point
138V (280V) resets to Utility Power at 132V (270V) or lower
Voltage Regulation
N/-2%
Frequency Range
60Hz: 54 - 66Hz or 50Hz: 44 - 56Hz
OUTPUT BATTERY OPERATION
Voltage Regulation
N/-2% (until Low Battery Warning)
Voltage T.H.D.
<3% (Linear Load)
+/-5% @ 100% Load change in 30 ms
Dynamic Response
Slew Rate
<1Hz / second
Overload Capacity
>115% - <125% for 60-seconds
>125% - <150% for 30-seconds
>150% for 1-second
ED2000RM2U
ED2000RMT2U
ED3000RM2U
ED3000RMT2U
2000VA/1600W 3000VA/2100W
80 - 138VAC
(160 - 280VAC)
Power Factor Correction
>97% at Full Load
Crest Factor
3 : 1