INSTALLATION PLACEMENT
This UPS series is intended to be install in a temperature controlled environ-
ment that is free of conductive contaminants. Select a location which will
provide good air circulation for the UPS at all times. Avoid locations near heat-
ing devices, water or excessive humidity, or where the UPS is exposed to direct
sunlight. Route power cords so they cannot be walked on or damaged.
Operating Temperature (Maximum): 0 to 40 degrees C (+32 to +104 degrees F)
Operating Elevation: 0 to 3,000m (0 to +10,000 ft)
Operating and Storage Relative Humidity: 95%, non-condensing
Storage Temperature: -15 to +45 degrees C (+5 to +113 degrees F)
Storage Elevation: 0 to 15,000m (0 to +50,000 ft)
REAR PANEL
INSTALLATION
Be sure to read the installation placement and all the cautions before installing
the UPS. Place the UPS in the final desired location and complete the rest of
the installation procedure. These UPSs are shipped with the internal batteries
disconnected. The batteries must be connected before putting these UPSs
into service. Follow the procedure below to connect the batteries and install
the UPS into the rack. USE CAUTION: The UPS is heavy. Use the appropri-
ate number of personnel when installing the UPS.
Output Power Receptacles
ED1000RM2U
NEMA 5-15P
Model #
ED2000RM2U
ED3000RM2U
ED1500RM2U
Input Power Plug
(All power cords are 10ft)
ED1000RMT2U
ED1500RMT2U
NEMA 5-15P
NEMA 5-20P
NEMA L5-30P
NEMA 6-15P
NEMA 6-15P
6-NEMA 5-15R
6-NEMA 5-15R
6-NEMA 5-15/20R
1-NEMA L5-20R
4-NEMA 6-15R
6-NEMA 5-15/20R
1-NEMA L5-30R
4-NEMA 6-15R
1. The input power cord (120V models). The AC Power Inlet IEC320 (208V models).
2. The input circuit breaker will trip in the event the load exceeds the UPS’s power rating.
3. The option slot is for option cards.
4. The Battery Backup output power receptacles. The output receptacles are electrically wir-
ed into two segments to support the "Load Shedding Function". The locking receptacle d-
oes not support the Load Shedding Function. NOTE: The locking recptacle is not on all
models.
5. The External Battery Connector is for connecting External Battery Packs.
6. The output circuit breaker will trip in the event the load exceeds the UPS’s power rating.
7. The USB Communications Interface Port is for UPS monitoring and control.
8. RS232 Communications Interface Port is for UPS monitoring and control.
9. The RJ11 REPO (Remote Emergency Power Off) Port is for UPS control.
10. The R-J11/R-J45 modular connectors are used for 10/100 Base-T Network/single line Pho-
ne/Fax/Modem protection.
11. External Ground Stud for connecting an external ground wire.
ED2000RMT2U
NEMA L6-20P
4-NEMA 6-15/20R
1-NEMA L6-20R
ED3000RMT2U
NEMA L6-30P
4-NEMA 6-15/20R
1-NEMA L6-30R