14
15
English
English
CHARGING THE BATTERY
The UPS will charge the internal batteries whenever the UPS is connected to
an AC source
a
nd there is an acceptable AC voltage present. NOTE: The input
circuit breaker MUST be in the on position for the 208V models. It is recom-
mended that the UPS's batteries be charged for a minimum of 4 hours before
use. The UPS may be used immediately, however, the “On-Battery” runtime
may be less than normally expected. NOTE: If the UPS is going to be out of
service or stored for a prolonged period of time, the batteries must be recharged
for at least twenty-four hours every ninety days.
COMMUNICATIONS PORT CONNECTION (OPTIONAL)
The Power Monitoring Software and interface cables can be used with the UPS.
Use only the interface cables that come with these UPSs. Connect the inter-
face cable (Serial or USB) to the appropriate communications port on the rear
panel of the UPS. Connect the other end of the cable to the device that will be
monitoring/controlling the UPS. NOTE: Connecting to the Communications
Port is optional. The UPS works properly without this connection.
CONNECTING THE UPS TO AN AC SOURCE
Plug the UPS into a two pole, three wire, grounded receptacle only. Do not use
extension cords, adapter plugs, or surge strips.
NETWORK/PHONE/FAX/MODEM PROTECTION CONNECTION (OPTIONAL)
Connect a 10/100 Base-T network, single line phone, Fax or Modem line to the
RJ11/45 protection sockets on the rear panel of the UPS. This connection will
require another length of telephone or network cable. The cable coming from
the telephone service or networked system is connected to the port marked
“IN”. The equipment to be protected is connected to the port marked "OUT".
NOTE: Connecting to the Network/Phone/Fax/Modem protection socket con-
nection is optional. The UPS works properly without this connection.
CONNECTING YOUR EQUIPMENT
Plug the equipment into the output receptacles on the rear panel of the UPS.
Do not use extension cords, adapter plugs or surge strips on the output of the
UPS. Ensure that you do not exceed the maximum output rating of the UPS
(refer to the information label on the UPS or the Electrical Specifications in this
manual).
CAUTION!
DO NOT connect a laser printer to the output receptacles on the
UPS, unless the UPS is rated 2000VA or greater. A laser printer
draws significantly more power when printing than at idle and
may overload the UPS.
RJ11 REPO (Remote Emergency Power Off) PORT (OPTIONAL)
Connect one end of the RJ11 cable to the REPO port and the other end of the
RJ11 cable to the EPO switch. In the AC or the Battery mode short pin4 to pin5
for approximately 0.5-seconds to shutdown the UPS. The UPS must be turned
off and then back on again to restart the UPS. NOTE: Connecting to the
REPO port is optional. The UPS works properly without this connection.
ON / Test Button
NOTE: The input circuit breaker MUST be in the on position for the 208V
models. Press the ON/Test Button for 1-beep (2-seconds) to turn the UPS on
and supply power to the load. In the AC mode press the ON/Test Button for 1-
beep (2-seconds) to perform a battery test. In the Battery mode press the ON/
Test Button for 1-beep (2-seconds) to silence the audible alarm. The UPS will
continue to charge the batteries whenever it is plugged into a wall outlet and
there is acceptable AC voltage present.
SYSTEM OVERVIEW
This On-Line UPS protects computers, servers, internetworking, and telecom-
munications equipment from blackouts, brownouts, overvoltages, and surges.
This On-Line UPS converts the input AC to DC and then back to a True Sine
Wave AC output. The True Sine Wave output is regulated within 2% of the
nominal output voltage. The Power Factor Correction (PFC) circuitry corrects
the input power factor to within 97% of unity and blocks the load generated
harmonic distortion from getting back on the input AC line. This On-Line UPS
provides a continuous true sine wave output with zero transfer time and great
regulation to protect your mission critical equipment. The UPS will quietly and
confidently protect your system from power anomalies.
The UPS will charge the batteries with the UPS in the on or off position as long
as the UPS is plugged into the AC wall outlet and there is an acceptable AC
voltage present (80/90 - 138VAC/160 - 280VAC). NOTE: The input circuit
breaker MUST be in the on position for the 208V models. When a blackout,
brownout, or an overvoltage condition occurs; the UPS will transfer to the bat-
tery mode, the On-Battery indicator will illuminate and the audible alarm will
sound once every ten-seconds indicating that the commercial power is lost or
unacceptable. When the commercial power returns or is at an acceptable
level, the UPS will automatically transfer back to the normal On-Line mode and
start recharging the batteries. During an extended outage when there is ap-
proximately two-minutes of backup time remaining the audible alarm will sound
twice every five-seconds. This Low Battery Warning is letting the user know
that they should save all open files and turn off their computer. When the
batteries reach the predetermined level the UPS will automatically shutdown
protecting the batteries from over discharging. Once the commercial power
returns the UPS will automatically restart, providing safe usable power to the
connected equipment and start recharging the batteries.
Summary of Contents for ED1000RM2U
Page 17: ...30 English Notes...