3.6.8.1.12  Press and hold the On Switch (on the front panel of the UPS) for 

approximately 3-seconds, then release. The audible alarm will sound 2-
beeps. The UPS will perform its normal startup test. Once the startup is 
complete the UPS will be in the normal On-Line mode. 

NOTE:

 If the Maintenance Bypass Procedure is not followed in the correct order 

and step-by-step the UPS and/or the connected equipment could be damaged. 
 

4  Communication Port, EPO Port and Option Cards 

 
The communication port on the UPS provides RS232 communications for 
remote monitoring and control. 
 

4.1. 

RS232 Communication Port: 

 

Baud Rate

 

9600 bps

 

Data Length

 

8 bits

 

Stop Bit

 

1 bit

 

Parity

 

None

 

DB9 Pin 2 

RS232 Tx 

DB9 Pin 3

 

RS232 Rx 

DB9 Pin 5

 

Ground 

 

4.2. 

EPO (Emergency Power Off) Port 

 

Connect one end of a two-wire cable to the EPO port and the other end of the 
two-wire cable to an EPO switch, and then short pin1 to pin2 for 
approximately 1.0-second to shutdown the UPS in the AC or the Battery 
mode. The LCD display will display EPO and Line OFF every 6-seconds. The 
UPS must be turned off and then turned back on again to restart the UPS. 
Connecting to the EPO port is optional the UPS system operates properly 
without this connection. 
 

AC Mode Operation: 

While the UPS is in the normal AC mode apply the short to pin1 and pin2 for 
approximately 1.0-second. The UPS shuts down, the fans will still be on. In 
approximately 1-minute the fans will reduce speed. 
 
To restart the UPS: Press the Off switch on the front panel for 2-beeps then 
release. Turn the UPS’s input circuit breaker (on the rear panel) to the Off 
position. Wait for approximately 1-minute (until the fans turn off) then turn the 
input circuit breaker to the On position. The UPS will be in the Bypass mode. 
Press the On switch on the front panel for 2-beeps to turn the UPS on. 
 
 

 

31

DC Mode Operation: 

While the UPS is in the DC mode apply the short to pin1 and pin2 for 
approximately 1.0-second. The UPS shuts down, the fans will still be on. In 
approximately 1-minute the fans will reduce speed. 
 
To restart the UPS once the utility power returns: Press the Off switch on the 
front panel for 2-beeps then release. Turn the UPS’s input circuit breaker (on 
the rear panel) to the Off position. Wait for approximately 1-minute (until the 
fans turn off) then turn the input circuit breaker to the On position. The UPS 
will be in the Bypass mode. Press the On switch on the front panel for 2-
beeps to turn the UPS on. 
 

4.3. 

Option Cards 

 

The optional interfaces cards are ED6/10KVA Programmable Relay Card (Dry 
Contact Relay) and the SNMP card. When the option cards are used in 
conjunction with RS232 communications port on the rear panel, the shutdown 
command from the EPO port will get the highest priority for the control 
command, then the RS232 port, then the SNMP card, and then the 
ED6/10KVA Programmable Relay card gets the lowest priority. Also there is 
ENV PROBE for environmental monitoring. 

 

5  Power Monitoring Software 

 

The SentryPlus software that comes with the UPS is compatible with many 
operating systems such as Windows NT/2000/XP/2003, Red Hat Linux, Fedora 
Linux, SuSE Linux, and FreeBSD. 

 

5.1. 

Hardware Installation 

 

5.1.1 

Connect one end of the RS232 cable to the UPS communication port. 

5.1.2 

Connect the other end of the cable to the RS232 port on the computer. 

 

5.2. 

Software Installation 

 

5.2.1 

Refer to the software user’s manual on the software CD. 

Summary of Contents for Minuteman ED10000T

Page 1: ...Inc 1455 LeMay Drive Carrollton TX 75007 Phone 1 972 446 7363 Fax 1 972 446 9011 Internet minutemanups com UPS Sizing sizemyups com PN 34000356 R3 ED10000T ED10200T Parallel Redundant ON LINE SERIES U...

Page 2: ...Storage instruction 12 3 4 Installation of the Castor Covers 13 3 5 Wiring the Input and Output Connections 14 3 6 Operation and Setup Instructions 19 4 Communication Port EPO Port and Option Cards 30...

Page 3: ...tteries 1 1 12 CAUTION A disconnect switch must be provided by the user for the AC output circuit when the UPS s output is hardwired To reduce the risk of fire connect only to a circuit provided with...

Page 4: ...the UPS for remote control and monitoring 2 2 4 These UPS systems can be used in a Parallel Redundant application To operate these UPS systems in the Parallel Redundant mode requires the Parallel Redu...

Page 5: ...2 Er06 Output Short Circuit 33 Er08 DC Bus high voltage level abnormal 34 Er09 DC Bus low voltage level abnormal 35 Er10 Inverter Over current 36 Er11 UPS Overheated 37 Er12 Inverter Overload 38 Er13...

Page 6: ...9 2 4 Controls and Indicators 2 4 1 UPS Control panel A LCD Display B N 1 green LED illuminates when the UPS is operating in the Parallel Redundant mode C Bypass green LED illuminates when the bypass...

Page 7: ...d by a qualified person If the package is deemed to be not usable immediately contact the freight carrier and the place of purchase USE CAUTION This UPS system is extremely heavy Always use the approp...

Page 8: ...000m 0 to 50 000 ft 3 3 Storage Instruction For extended storage with moderate climates the batteries should be charged for 12 hours every 3 months Repeat this procedure every 2 months under high temp...

Page 9: ...to the terminal blocks 3 5 1 1 1 OUTPUT connections for ED10000T Hardwired only Configurations 1 7 are for Hardwiring the output of ED10000T A Qualified Electrical Contractor must perform the hardwir...

Page 10: ...KVA max load per circuit and one 208VAC 10KVA circuit Total combined output load not to exceed 10KVA 1 Connect a jumper wire from L22 to N21 2 Circuit1 120VAC L22 Line N22 Neutral G2 Ground 3 Circuit2...

Page 11: ...to terminal G2 A Qualified Electrical Contractor must perform the hardwiring The outputs must be connected to an over current protection device circuit breaker of 50 amperes in accordance with the Nat...

Page 12: ...may be used immediately but the On Battery runtime maybe less than normally expected NOTE If the UPS is going to be out of service or stored for a prolonged period of time the batteries must be recha...

Page 13: ...ypass Input Drawing J Frequency from Utility Input Drawing K Frequency from Bypass Input Drawing L UPS Output Voltage Drawing M UPS Output Frequency Drawing N UPS Output Load Drawing O UPS Battery Vol...

Page 14: ...eck the UPS settings Drawing Q1 Buzzer audible alarm Drawing R1 Self test Drawing S1 Bypass Voltage Window Drawing T Output Frequency Synchronization Window Drawing U Inverter Output Voltage Drawing V...

Page 15: ...econds and then release the audible alarm will sound 2 beeps the LCD display screen shows as drawing Q1 then the UPS is under setting mode 3 6 5 2 Except for the Buzzer as drawing Q1 Q2 and the Self t...

Page 16: ...r on the rear panel of the Battery Pack 3 6 7 4 The UPS is OFF 3 6 7 5 To completely de energize the UPS disconnect the battery cable from the rear panel of the UPS Turn Off the utility circuit breake...

Page 17: ...on Wait for approximately 1 minute until the fans turn off then turn the input circuit breaker to the On position The UPS will be in the Bypass mode Press the On switch on the front panel for 2 beeps...

Page 18: ...er of the UPS The UPS should be unlocked but the original problem may not be resolved Call for Service 33 7 Replacing the Batteries QUALIFIED SERVICE PERSONNEL ONLY Please read all of the WARNINGS and...

Page 19: ...ining screws for the side panels on the rear panel of the UPS 7 1 9 Slide the side panels towards the rear of the UPS and lift up to remove the side panels and set aside FIG 2 FIG 1 FIG 2 35 7 1 10 Lo...

Page 20: ...37 7 1 32 Back to the right hand side of the UPS FIG 3 remove the piece of electrical tape from the end of battery positive Red wire Observer polarity Reconnect the battery positive Red wire NOTE Some...

Page 21: ...oltage let through as a percentage of an applied ANSI C62 41 Cat A 6KV 5 Noise Filter Normal and common mode EMI RFI suppression Audible Noise at 1 m 3 ft 50dB 160 280VAC at loads 50 of the rated capa...

Page 22: ...m the nearest authorized service center Replacement parts and warranty labor will be borne by Para Systems For equipment located outside of the United States and Canada Para Systems only covers faulty...

Page 23: ...Name Para Systems Inc MINUTEMAN UPS Manufacturer s Address 1455 LeMay Drive Carrollton Texas 75007 USA Type of Equipment Uninterruptible Power Supplies UPS Model No ED10000T ED10200T Year of Manufact...

Reviews: