background image

 

32

6 Troubleshooting 

Guide 

 

If the UPS malfunctions, check the followings: 

a. Is the wiring of the input and the output correct? 
b. Is the input voltage within the acceptable window of the UPS? 

If items a. and b. above are correct then proceed with the following chart. If the 
problem persists, see Obtaining Service. 

 

Situation Check 

Items 

Solution 

UPS Red Fault 
LED lights up   

Check the error code 
shown on the LCD 
screen 
 
1.Er05,     & 
2.Er06, Er10, Er12, 

Er28 &   

3.EPO 
4.Er11, Er33 
5.Er14 
6.

Er16, Er27 

7.Er21 
8.other error code 
 

1. Check to see if the battery connection is 

properly done, then re-charge the 
batteries for 8-hours to see whether the 
UPS will backup normally; call for 
service. 

2. Remove some of the load from the UPS 

output. Check the Input power cord. 

3. Remove the short circuit at the EPO 

terminal. 

4. 

Remove all objects that block the 
ventilation holes. 

5. Check the fans on rear panel. 
6. All of parameters except the ID number 

in the parallel UPS must be same. 

7. Reconnect the RJ-45 wire or set a UPS 

with ID=1. 

8. Call for Service. 

UPS fails to offer 
battery backup or 
its runtime is to 
short. 

The batteries maybe 
weak or at the end of 
useful service life. 

Charge the batteries for 8-hours, then 
retest. If the runtime is still less than 
expected, the batteries need to be 
replaced. Contact your local distributor. 

The UPS is in 
the Bypass or 
the On-Line 
mode there are 
no Error codes or 
faults and there 
is no output 
voltage at the 
terminal blocks. 

Thermal Circuit Breaker 
CB3 has been tripped. 

Turn off the UPS. Turn the Input circuit 
breaker on the rear panel to the Off 
position. Ensure the Maintenance Bypass 
Switch is in the “INV” position. Remove the 
two retaining screws from CB3’s cover 
plate. Reset the Thermal Circuit Breaker 
CB3. 

UPS locks itself 
and it cannot be 
turned off. 

To unlock the UPS 
press the OFF switch 
for 5-seconds and the 
audible alarm will sound 
2-beeps. Turn Off the 
input circuit breaker of 
the UPS. 

The UPS should be unlocked, but the 
original problem may not be resolved. Call 
for Service. 

 

 

33

7  Replacing the Batteries 

(QUALIFIED SERVICE PERSONNEL ONLY) 

Please read all of the 

WARNINGS

 and 

CAUTIONS

 before attempting to 

service the batteries. 
 

WARNING:

 This Uninterruptible Power Supply contains potentially hazardous 

voltages. Do not attempt to disassemble the UPS system beyond the battery 
replacement procedure. This UPS system contains no user serviceable parts. 
Maintenance and Battery replacement must be performed by

 QUALIFIED 

SERVICE PERSONNEL ONLY. 

 

CAUTION:

 Do not open or mutilate batteries. Released electrolyte is harmful to 

the skin and eyes and may be toxic. 
 

CAUTION:

 Do not dispose of batteries in a fire. The batteries may explode. 

 

CAUTION:

 The batteries in this UPS are recyclable. Dispose of the batteries 

properly. The batteries contain lead and pose a hazard to the environment and 
human health if not disposed of properly. Refer to local codes for proper 
disposal requirements or return the battery to the supplier. 
 

CAUTION:

 The battery system voltage is 240VDC and can present a risk of 

electrical shock. These batteries produce sufficient current to burn wire or tools 
very rapidly, producing molten metal. Observe these precautions when 
replacing the batteries: 

1.  Remove watches, rings, or other metal objects. 
2.  Use hand tools with insulated handles. 
3.  Wear protective eye gear (goggles), rubber gloves and boots. 
4.  Do not lay tools or other metal parts on top of batteries. 
5.  Disconnect the charging source prior to connecting or disconnecting 

the battery terminals. 

6.  Determine if the battery is inadvertently grounded. If the battery is, 

remove the source of the grounding. Contact with any part of a 
grounded battery can result in an electrical shock. The likelihood of 
such shock will be reduced, if such grounds are removed during 
installation and maintenance. 

 

CAUTION:

 Replace the batteries with the same number and type as originally 

installed. These batteries have pressure-operated vents. These batteries 
contain sealed non-spillable maintenance-free lead acid batteries. 
 
 

 

Summary of Contents for Minuteman ED10000T

Page 1: ...Inc 1455 LeMay Drive Carrollton TX 75007 Phone 1 972 446 7363 Fax 1 972 446 9011 Internet minutemanups com UPS Sizing sizemyups com PN 34000356 R3 ED10000T ED10200T Parallel Redundant ON LINE SERIES U...

Page 2: ...Storage instruction 12 3 4 Installation of the Castor Covers 13 3 5 Wiring the Input and Output Connections 14 3 6 Operation and Setup Instructions 19 4 Communication Port EPO Port and Option Cards 30...

Page 3: ...tteries 1 1 12 CAUTION A disconnect switch must be provided by the user for the AC output circuit when the UPS s output is hardwired To reduce the risk of fire connect only to a circuit provided with...

Page 4: ...the UPS for remote control and monitoring 2 2 4 These UPS systems can be used in a Parallel Redundant application To operate these UPS systems in the Parallel Redundant mode requires the Parallel Redu...

Page 5: ...2 Er06 Output Short Circuit 33 Er08 DC Bus high voltage level abnormal 34 Er09 DC Bus low voltage level abnormal 35 Er10 Inverter Over current 36 Er11 UPS Overheated 37 Er12 Inverter Overload 38 Er13...

Page 6: ...9 2 4 Controls and Indicators 2 4 1 UPS Control panel A LCD Display B N 1 green LED illuminates when the UPS is operating in the Parallel Redundant mode C Bypass green LED illuminates when the bypass...

Page 7: ...d by a qualified person If the package is deemed to be not usable immediately contact the freight carrier and the place of purchase USE CAUTION This UPS system is extremely heavy Always use the approp...

Page 8: ...000m 0 to 50 000 ft 3 3 Storage Instruction For extended storage with moderate climates the batteries should be charged for 12 hours every 3 months Repeat this procedure every 2 months under high temp...

Page 9: ...to the terminal blocks 3 5 1 1 1 OUTPUT connections for ED10000T Hardwired only Configurations 1 7 are for Hardwiring the output of ED10000T A Qualified Electrical Contractor must perform the hardwir...

Page 10: ...KVA max load per circuit and one 208VAC 10KVA circuit Total combined output load not to exceed 10KVA 1 Connect a jumper wire from L22 to N21 2 Circuit1 120VAC L22 Line N22 Neutral G2 Ground 3 Circuit2...

Page 11: ...to terminal G2 A Qualified Electrical Contractor must perform the hardwiring The outputs must be connected to an over current protection device circuit breaker of 50 amperes in accordance with the Nat...

Page 12: ...may be used immediately but the On Battery runtime maybe less than normally expected NOTE If the UPS is going to be out of service or stored for a prolonged period of time the batteries must be recha...

Page 13: ...ypass Input Drawing J Frequency from Utility Input Drawing K Frequency from Bypass Input Drawing L UPS Output Voltage Drawing M UPS Output Frequency Drawing N UPS Output Load Drawing O UPS Battery Vol...

Page 14: ...eck the UPS settings Drawing Q1 Buzzer audible alarm Drawing R1 Self test Drawing S1 Bypass Voltage Window Drawing T Output Frequency Synchronization Window Drawing U Inverter Output Voltage Drawing V...

Page 15: ...econds and then release the audible alarm will sound 2 beeps the LCD display screen shows as drawing Q1 then the UPS is under setting mode 3 6 5 2 Except for the Buzzer as drawing Q1 Q2 and the Self t...

Page 16: ...r on the rear panel of the Battery Pack 3 6 7 4 The UPS is OFF 3 6 7 5 To completely de energize the UPS disconnect the battery cable from the rear panel of the UPS Turn Off the utility circuit breake...

Page 17: ...on Wait for approximately 1 minute until the fans turn off then turn the input circuit breaker to the On position The UPS will be in the Bypass mode Press the On switch on the front panel for 2 beeps...

Page 18: ...er of the UPS The UPS should be unlocked but the original problem may not be resolved Call for Service 33 7 Replacing the Batteries QUALIFIED SERVICE PERSONNEL ONLY Please read all of the WARNINGS and...

Page 19: ...ining screws for the side panels on the rear panel of the UPS 7 1 9 Slide the side panels towards the rear of the UPS and lift up to remove the side panels and set aside FIG 2 FIG 1 FIG 2 35 7 1 10 Lo...

Page 20: ...37 7 1 32 Back to the right hand side of the UPS FIG 3 remove the piece of electrical tape from the end of battery positive Red wire Observer polarity Reconnect the battery positive Red wire NOTE Some...

Page 21: ...oltage let through as a percentage of an applied ANSI C62 41 Cat A 6KV 5 Noise Filter Normal and common mode EMI RFI suppression Audible Noise at 1 m 3 ft 50dB 160 280VAC at loads 50 of the rated capa...

Page 22: ...m the nearest authorized service center Replacement parts and warranty labor will be borne by Para Systems For equipment located outside of the United States and Canada Para Systems only covers faulty...

Page 23: ...Name Para Systems Inc MINUTEMAN UPS Manufacturer s Address 1455 LeMay Drive Carrollton Texas 75007 USA Type of Equipment Uninterruptible Power Supplies UPS Model No ED10000T ED10200T Year of Manufact...

Reviews: