Matrix2000

Installation & Operation Manual - CPD

Advanced Analog Fire Alarm Control Panel

Repeaters 4 – 24 Zones

Version:

 1.0

Revision:

 0

Repeaters

Summary of Contents for MATRIX RPT 12Z

Page 1: ...Matrix2000 Installation Operation Manual CPD Advanced Analog Fire Alarm Control Panel Repeaters 4 24 Zones Version 1 0 Revision 0 Repeaters ...

Page 2: ... be used in conjunction with products not man ufactured by Paradox Hellas Paradox Hellas cannot guarantee the performance of the fire alarm system and shall not be responsible in any way whatsoever for faulty installation or connection RoHS directive compliance The EC RoHS guideline has been released in order to reduce the heavy metal load in electrical and electronic products caused by e g lead a...

Page 3: ...dications and Controls 7 4 1 Central Electric Keyswitch 8 5 Micro switches SW1 8 6 Communication modules connection 9 6 1 MRS232 485 communication module 9 6 1 1 Components Identification 9 6 1 2 General Description 10 6 2 MRTCP IP communication module 10 6 2 1 Components Identification 10 6 2 2 General Description 11 Appendix A Panel Specifications 12 TABLE OF CONTENTS ...

Page 4: ......

Page 5: ... zones JP3 3 Connection to 3rd repeater s keypad 20 or 24 zones 28 VDC 4 Secondary power source for repeaters installed far away from the Ma trix2000 fire alarm panel 4 wire bus connector to main board 5 Connects the repeater with the Matrix2000 fire alarm panel JP7 6 3 pin header for selecting power source via the 28VDC bock connector or via 4 wire Vbus connector JP4 7 2 pin header for RS 232 ter...

Page 6: ...are the site Make sure the installation location is free from construction dust debris extreme temperature ranges and humidity Unpack the equipment Install the cabinet See Installing the cabinet for cabinet dimensions Install optional components Review wire routing Connect the field wiring Check for opens grounds and shorts before connecting Connect ground then AC power Ensure that the AC circuit ...

Page 7: ...3 cm Table 2 Framing and mounting dimensions 4 Keyboard Indications and Controls Operating monitoring and programming of the panel is performed in three different ac cess levels In access level 1 the panel controls are locked Access to level 2 is achieved by the keyswitch on the face of the panel Operations at access level 2 are performed with the keypad Access level 3 operations are accomplished ...

Page 8: ... of approximately 2 seconds all the system zones turn into Alarm Evacuation Mode resulting in the activation of all signaling devices in the protected area The system returns to standby mode by turning the key to the Control Enable position and pressing the system RESET button The key from the Keyswitch can be removed only when the keyswitch is in the Normal position For additional information ple...

Page 9: ...ith a jumper connects a 120 Ohm resistor to the bus as the termination device Only place this jumper to last unit in the RS485 chain For short bus distances this jumper is not needed 6 Communication modules connection 6 1 MRS232 485 communication module 6 1 1 Components Identification 1 2 3 4 5 Figure 5 MRS232 485 communication module Connector FROM MAIN BOARD 1 Connects the MRS232 485 module with...

Page 10: ...ted JP2 must be closed MRS232 485 module ViewMatrix Figure 6 MRS232 485 module connection diagram This module also provides the Matrix2000 panels the ability to connect to a local PC through it s serial port Monitoring and control of the system from a PC can be performed with the aid of specially developed software ViewMatrix running under Microsoft s Win dows This software simulates the keyboard ...

Page 11: ...connector Connector 6 Connects the MRTCP IP module with the Matrix2000 fire alarm panel s main board via flat cable 6 2 2 General Description The MRTCP IP module connects directly to the main board of the Matrix2000 panel Provides full access and control of the panel either locally via RS485 serial connection to repeaters or via internet TCP IP to any PC running the specially designed software Vie...

Page 12: ...Repeater current draw standby 35 mA 35 mA 35 mA 35 mA 35 mA 35 mA Max current con sumption 100 mA 200 mA 300 mA 400 mA 500 mA 600 mA Power Supply 28 VDC Secondary power supply 28 VDC Environmental Temperature 2 to 45 C 32 to 120 F Humidity 5 to 95 RH non condensing Terminal rating All terminals rated for 12 to18 AWG 0 75 to 2 5 sq mm ...

Page 13: ...witch of the keyboard to Con 2 trol Enable Press Reset 3 TO PERFORM A LAMP TEST panel and re mote annunciators Press and hold the Test button 1 RESPONDING TO TROUBLE SIGNALS Turn the keyswitch of the keyboard to Con 1 trol Enable Silence the panel buzzer 2 Investigate the cause of the trouble and 3 notify the authorized service personnel im mediately TO SILENCE THE PANEL BUZZER Press Panel Silence...

Page 14: ...__________________________ Zone 12 ______________________________________________________________________ Zone 13 ______________________________________________________________________ Zone 14 ______________________________________________________________________ Zone 15 ______________________________________________________________________ Zone 16 _________________________________________________...