8
Matrix2000 repeaters
4.1 Central Electric Keyswitch
The electrical keyswitch allows the operation of the panel in access level 2 as well as the
activation of the immediate evacuation (an access level 2 action).
The central electric Keyswitch has three positions:
1
st
position (Access Level 1)
Normal
: This is the Normal operation mode. The panel
waits for alarm events or any faults that may develop in the installation. All buttons on
the keypad are
disabled
.
2
nd
position (Access Level 2)
Control Enable
: Alarm events and possible faults are de-
tected, all buttons on the keypad are
active
and the system is controllable.
For Normal operation the keyswitch must be in the 1
st
position.
3
rd
position (Access Level 2)
Evacuate
: After a small delay of approximately 2 seconds
all the system zones turn into Alarm Evacuation Mode resulting in the activation of all
signaling devices in the protected area. The system returns to standby mode by turning
the key to the
Control Enable
position and pressing the system
RESET
button.
The key from the Keyswitch can be removed only when the keyswitch is in the
Normal
position.
For additional information please refer to Matrix2000 Installation & Operation manu-
al.
5. Micro switches SW1
Up to 7 repeaters may be connected to the Matrix bus. Each connected repeater must
have a unique address from 1 to 7. This address is set by 3 dip switches located on the
repeater PCB (see figure 4 below). To select the required address the switches 6 to 8
must be set as shown in table 3 below
This procedure must be performed only by the
installation engineer
.
Figure 4.
Micro switches module SW1
All switches that are not used must be left to the OFF position.