9
Matrix2000 repeaters
SW1-6
SW1-7
SW1-8
Address
OFF
OFF
ON
1
OFF
ON
OFF
2
OFF
ON
ON
3
ON
OFF
OFF
4
ON
OFF
ON
5
ON
ON
OFF
6
ON
ON
ON
7
Table 3.
Repeater’s address setup
The maximum distance that a repeater can be connected is 600 meters. The use of good
quality UTP cable is recommended. Always use one twisted pair for the A/B signals of
the RS485 bus. This provides the best noise rejection and maximum long distance reli-
ability. Jumper JP4, a two pin header, when shorted with a jumper, connects a 120 Ohm
resistor to the bus as the termination device. Only place this jumper to last unit in the
RS485 chain. For short bus distances this jumper is not needed.
6. Communication modules connection
6.1 MRS232/485 communication module
6.1.1 Components Identification
1
2
3
4
5
Figure 5.
MRS232/485 communication module
Connector “FROM MAIN BOARD”:
1.
Connects the MRS232/485 module with the
Matrix2000 fire alarm panel’s main board via flat cable.
JP2:
2.
2-pin header for 485 line termination.
4-wire bus connector to main board:
3.
Connects the MRS232/485 module with the
Matrix2000 fire alarm panel.
RS-232 connector.
4.
JP5:
5.
2-pin header for the RS-232 shut down.