background image

 

DGP-848 Control Panel

 

7

2.12 Double Zone Connections

Enabling the ATZ feature (see section 4.8 on page 16) allows you 
to install two detection devices per input terminal. The ATZ feature 
is a software oriented feature. Simply connect the devices as 
shown in Figure 8. Devices connected to input terminals must be 
assigned to a zone and the zone's parameters must be defined. 
Please refer to Zone Programming on page 11. for more 
information. For UL listed installations, use EOL resistor part 
#2011002000.

Figure 8: Double Zone Connections

2.13 Keypad Zone Connections

Each LED and LCD keypad has one hardwired input terminal 
allowing you to connect a detector or door contact directly to the 
keypad. For example, a door contact located at the entry point of 
an establishment can be wired directly to the input terminal of the 
entry point keypad instead of all the way to the control panel.

Even with the ATZ feature enabled in the control panel, 
only one device can be connected to the keypad’s 
hardwired input terminal. Tamper is not recognized on 
keypad zones. The keypad zone follows the control 
panel’s EOL definition.

A device connected to the keypad’s input terminal must be 
assigned to a zone in the control panel and the zone’s parameters 
must be defined (see Zone Programming on page 11.). The keypad 
will communicate the status of the zone to the control panel via the 
combus. The detection device is connected as shown in Figure 3 
on page 3.

2.14 Keyswitch Connections

Connect the keyswitches to the keypad, control panel, or Zone 
Expansion Module's hardwired input terminals as shown in Figure 
9. On
ce a keyswitch is connected, it must be assigned a keyswitch 
zone and its parameters must be defined as described in 
Keyswitch Programming on page 17.

Figure 9: Keyswitch Connections

2.15 Fire Circuits

Connect the smoke detectors used in the security system using 
any of the following methods. Smoke detectors connected to the 
control panel or zone expansion input terminals must be assigned 
to a zone in the control panel and the zone's parameters must be 
defined as a Fire Zone. For more details, refer to Zone 
Programming 
on page 11.

2.15.1 Smoke Detector Installation (2-Wire)

PGM1 can be defined as a 2-wire smoke detector input (see 
section 10.4 on page 31) enabling smoke detectors to be 
connected as shown in Figure 10 on page 8. Fire Zones must use 
a 1k

 EOL resistor. If there is a line short or if the smoke detector 

becomes active, whether the system is armed or disarmed, the 
control panel will generate an alarm. If the line is open, the “Zone 
Fault” trouble indication will appear in the Trouble Display and will 
transmit the appropriate report code to the monitoring station (if 
programmed).

2.15.2 ESL CleanMe

TM 

Installation

The Digiplex control panel supports the use of ESL smoke 
detectors that have the CleanMe

TM

 feature. The ESL smoke 

detectors are connected exactly like standard smoke detectors as 
shown in Figure 10 on page 8. Please note that you should avoid 
connecting more than 20 ESL smoke detectors. When an ESL 

Summary of Contents for Digiplex DGP-848

Page 1: ...Digiplex Control Panel DGP 848 V4 1 Reference and Installation Manual Includes DGP2 641BL RB Installation Instructions DGP 848...

Page 2: ......

Page 3: ...ch Features 20 Exit Delay 20 Keypad Lock out Feature 20 Maximum Bypass Entries 21 Display Bypass If Armed 21 Bell Squawk 21 Ring back 21 Switch To Stay Arming 21 Always Force Arm When Regular Arming 2...

Page 4: ...Access Levels 42 Schedules 42 Holiday Programming 42 Logging Access Control Events 42 Global Access Door Features 43 WinLoad Software 44 Answering Machine Override 44 Ring Counter 44 Panel Identifier...

Page 5: ...ne combus for up to 95 modules All modules have Plug and Play capability Connect modules up to 3000ft 914m from the panel Full supervision and sabotage proof technology without additional wiring Up to...

Page 6: ...nds If the battery is disconnected if its capacity is too low or if the battery voltage drops to 10 5 volts or less when there is no AC the Battery Trouble message will appear in the Trouble Display A...

Page 7: ...To metallic enclosure To provide maximum lightning protection we strongly recommend having separate earth connections for the dialer and zone ground terminals COMBUS AUX POWER Refer to transformer req...

Page 8: ...ontact Modules DGP2 ZC1 _______ X 30mA __________ mA 1 Zone Expansion Modules DGP2 ZX1 _______ X 30mA __________ mA 4 Zone Expansion Modules APR3 ZX4 _______ X 30mA __________ mA 8 Zone Expansion Modu...

Page 9: ...0ft Magellan Module MG RCV3 A 35mA LCD Keypad DGP2 641BL D 110mA 15m 50ft 7 5m 25ft 7 5m 25ft 15m 50ft Motion Detector Module DGP2 70 E 30mA LED Keypad DGP2 648 F 110 mA LED Keypad DGP2 648 G 110 mA A...

Page 10: ...would exceed the system s capacity For information on how to assign a detection device to a zone in the control panel please refer to Zone Programming on page 11 Before connecting a module to the cont...

Page 11: ...shown in Figure 3 on page 3 2 14 Keyswitch Connections Connect the keyswitches to the keypad control panel or Zone Expansion Module s hardwired input terminals as shown in Figure 9 Once a keyswitch i...

Page 12: ...elay will cause the control panel to transmit the Fire Loop Trouble report if programmed in section 707 To reset unlatch the smoke detector after an alarm verify that the negative of the smoke detecto...

Page 13: ...the right action key Exit on Grafica keypads as many times as needed to return to the desired screen Please note that a module s serial number can be located on the module s PC board or it may already...

Page 14: ...that the write protect jumper is on 3 Enter section 965 to copy the contents of the panel except sections 001 to 048 device serial numbers and 049 to 056 keyswitch serial numbers to the key 966 to co...

Page 15: ...esent zones 1 to 48 respectively Zone Parameters Sections 101 to 148 represent zones 1 to 48 respectively Enter the 8 digit SERIAL NUMBER of the addressable detection device or module that has a hardw...

Page 16: ...ry Delay 1 Timer 230 Entry Delay 2 Timer 231 Entry Delay 3 Timer 232 Entry Delay 4 Timer 233 Please note these are the same timers used for Stay Delay zones see section 4 2 9 on page 13 Entry Delay zo...

Page 17: ...lay 4 Timer in section 233 Please note that the Entry Delay Timers are the same timers used for Entry Delay zones 4 3 Zone Partition Assignment SECTIONS 101 TO 148 SECOND DIGIT 1 TO 4 The control pane...

Page 18: ...digit delay value 010 to 255 seconds into section 200 Fire Zones cannot be set as Intellizones 4 4 7 Delay Alarm Transmission SECTIONS 101 TO 148 OPTION 8 When an alarm condition occurs on a zone wit...

Page 19: ...Panel 15 Table 5 Hebrew Keypad Letter Assignment Table 6 Russian Keypad Letter Assignment Table 7 Special Characters Catalogue Table 8 Hebrew Special Characters Catalogue Table 9 Russian Special Chara...

Page 20: ...t 004 speed 205 Panel Terminal 5 Input 005 speed 206 Panel Terminal 6 Input 006 speed 207 Panel Terminal 7 Input 007 speed 208 Panel Terminal 8 Input 008 speed 209 Panel Doubler 1 Input 009 speed 210...

Reviews: