16
Reference & Installation Manual
4.6 Input Speed
S
ECTIONS
[201]
TO
[216]
(000 to 255 X 20msec
,
default: 600ms) The Input Speed defines
how quickly the control panel will respond to an open zone
detected on any hardwired input terminal. The control panel will not
display and/or respond to an open zone until the programmed Input
Speed elapses to prevent glitches from causing an alarm or
unnecessary reporting. All other zone definitions and options do
not come into effect until the Input Speed has elapsed. The Input
Speed does not apply to addressable detection devices. The Input
Speed for each input terminal can be set from 20ms to 5.1s, by
programming the desired value (001 to 255 X 20ms) into the
appropriate section.
Example:
The system is armed and the zone speed is set for 600ms. A zone
opens and closes in less than 600ms, the control panel will not
respond (i.e. no reporting, no alarm and no display on the keypad).
[201]
Panel Terminal 1 / Input 001 speed
[202]
Panel Terminal 2 / Input 002 speed
[203]
Panel Terminal 3 / Input 003 speed
[204]
Panel Terminal 4 / Input 004 speed
[205]
Panel Terminal 5 / Input 005 speed
[206]
Panel Terminal 6 / Input 006 speed
[207]
Panel Terminal 7 / Input 007 speed
[208]
Panel Terminal 8 / Input 008 speed
[209]
Panel Doubler 1 / Input 009 speed
[210]
Panel Doubler 2 / Input 010 speed
[211]
Panel Doubler 3 / Input 011 speed
[212]
Panel Doubler 4 / Input 012 speed
[213]
Panel Doubler 5 / Input 013 speed
[214]
Panel Doubler 6 / Input 014 speed
[215]
Panel Doubler 7 / Input 015 speed
[216]
Panel Doubler 8 / Input 016 speed
4.7 EOL Zones
S
ECTION
[504]: O
PTION
[7]
If detection devices connected to hardwired input terminals use
1k
Ω
end of line resistors, enable option [7] in section [504]. For
more information on the use of EOL resistors, refer to Zone
Connections in section 2.11 on page 6 & section 2.12 on page 7.
4.8 Zone Doubling (ATZ)
S
ECTION
[504]: O
PTION
[8]
Enabling the ATZ feature allows you to install two detection devices
per hardwired input terminal. Each detection device will have its
own zone, display its zone status on the keypad and send separate
alarm codes for each zone. The extra zones are recognized as
described in Figure 17. For information on how to connect the
detection devices, please refer to Double Zone Connections in
section 2.12 on page 7. Fire Zones cannot be doubled.
Figure 17: ATZ Input Terminal Recognition