"NO MOVEMENT"
If a time is programmed at address 253, and a report code is entered at address 190 (SECTION 32), the
panel will send a report to the central if no movement takes place in the protected area for a designated
time period.
"LATE TO CLOSE"
If the system is not armed by a specified time (addresses 245, 246) the code programmed at address
190 (SECTION 32) will be transmitted.
AUTO ARMING
The panel can be programmed to automatically arm itself every day in two ways: at the same time pro-
grammed for the auto test report (addresses 245, 246) and/or once the "no movement" delay has
elapsed (address 253). To program "auto arming", go to address 206 and enable key [5] (auto arm on
time), and/or key [6] (auto arm on "no movement"). All zones must be closed in order for system to auto
arm. If panel fails to auto arm the "no movement/late to close" report will be transmitted.
Note: The "auto arm" report is programmed at address 188, SECTION 32.
OPERATIONAL NOTE REGARDING SPECIAL TIMING FUNCTIONS
The time programmed at addresses 245, 246 can be used to:
1 Auto-arm the system and if programmed, transmit the arming code at address 188 (SECTION 32)
2. Specify the time of day for the Test Report, the code programmed at address 175 (SECTION 28)
3. Transmit the Late to Close/No Movement code, address 190 (SECTION 32), if the system is not
armed.
The amount of time programmed at address 253 (Max = 63.75 hours) can be used to;
1. Transmit the Late to Close/No Movement code, address 190 (SECTION 32), if there is no move-
ment in the protected area while the system is disarmed.
2. Auto-arm the system and if programmed, transmit the arming code at address 188 (SECTION 32)
after transmitting the Late to Close/No Movement code (as above).
The "late to close/no movement" code programmed at address 190 (SECTION 32) will be transmitted;
1. at the time programmed at addresses 245, 246 if the system is not armed (Late to Close).
2. after the time programmed at address 253 expires (No Movement).
The amount of time programmed at address 254 (Max = 127 minutes) can be used to:
1. keep a programmable output (PGM) active for up to 127 minutes after a certain event.
20
IM8