Magellan & Spectra SP • Programming Guide
69
General Zone Options
Miscellaneous System Options
System Timers
Table 61: Description of options 3 & 4 and 6 & 7, in section [705]
Option
Description
3
4
RF Zone/Hardwired Zone Tamper Recognition Options
Keypad/Bus Module Tamper Recognition Options*
OFF
OFF
Disabled
Disabled
OFF
ON
Trouble only
Trouble only
ON
OFF
When disarmed: trouble only; when armed: follow zone’s alarm type
Trouble only
ON
ON
When disarmed: audible alarm; when armed: follow zone’s alarm type
Audible alarm
6
7
RF Zone Supervision Options
Keypad/Bus Module Supervision Options
OFF
OFF
Disabled
Disabled
OFF
ON
Trouble only
Trouble only
ON
OFF
When disarmed: trouble only; when armed: follow zone’s alarm type
Trouble only
ON
ON
When disarmed: audible alarm; when armed: follow zone’s alarm type
Audible alarm
* Tamper recognition of keypad/bus module, only if section
[700]
, option 7, is enabled.
Table 62: Description of section [706]
Option
Description
OFF
ON
Se
ct
io
n
[706]
1
Check-in supervision time
24 hours
80 minutes
2
EOL resistors (applies to all hardwired zones – panel, keypad, ZX8/ZX82)
Disabled
Enabled
3
Zone input 1 becomes a two-wire smoke input (except SP4000, SP5500, and SP65)
Disabled
Enabled
4
ZX8/ZX82 ID A (panel + 1) input 1
Zone input
Tamper input
5
ZX8/ZX82 ID B (panel + 9) input 1
Zone input
Tamper input
6
ZX8/ZX82 ID C (panel + 17) input 1
Zone input
Tamper input
= Default
Table 63: Description of section [708]
Option
Description
OFF
ON
Se
c
ti
o
n
[708]
EN50131
OP
T
ION
S
1
Enter code to view trouble
One-touch
Enter code
2
Enter code to view alarm in memory/event list
One-touch
Enter code
3
Trouble latch
Disabled
Enabled
4
Bell squawk on Installer in
Disabled
Enabled
5
Acknowledge trouble(s) before arming
Disabled
Enabled
6
Do not arm if zone opens during exit delay
Disabled
Enabled
7
Disable ‘Bypass and Arm’
Disabled
Enabled
8
Future use
-
-
-
-
= Default
Worksheet 56: System Timers
Section
Data
Description
Section
Data
Description
[710]
___/___/___
000 to 255 seconds Entry delay 1* (default: 045)
[718]
___/___/___
000 to 255 seconds
Remote panic disarm lock delay
(default: 000)
[711]
___/___/___
000 to 255 seconds Entry delay 2* (default: 045)
[719]
___/___/___
000 to 255 days
Closing delinquency delay
(default: 000)
[712]
___/___/___
000 to 015
Auto-zone shutdown counter
(default: 005)
[720]
___/___/___
000 to 255 seconds Flex-instant delay (default: 015)
[713]
___/___/___
000 to 255 seconds Intellizone delay (default: 048)
[721]
___/___/___
000 to 255 seconds
For StayD: re-arm delay
(default: 005)
[714]
___/___/___
000 to 255 minutes Recycle alarm delay (default: 000)
[722]
___/___/___
000 to 255 seconds
Auto trouble shutdown**
(default: 010)
[715]
___/___/___
000 to 255
Recycle alarm counter
(default: 000)
[723]
___/___/___
000 to 255 seconds
Panic shutdown**
(default: 010)
* For EN 50131, the maximum value is 45 seconds.
** For EN 50131, the section must be set to a minimum of 3 and a maximum of 10