INTRODUCTION 

 
Thank you for purchasing the Parallax Model 

ATS501

 automatic RV Line/ Generator 

switch. We are confident that the 

ATS 501

 will give you outstanding performance for 

many years. If you have any questions or comments about this product, please contact 
Parallax’s customer service representative at the address or phone and fax numbers 
listed below.  
 
Parallax Power Supply  
100 West 11

th

 Street, Suite 100   Anderson, IN 46016 

Phone: 1-800-443-4859 
Fax. : 1-765-608-5235 

 

GENERAL INFORMATION 

 
The 

ATS 501 

is designed to automatically switch the on board 120 or 240 volt 

appliances to generator power when the generator is activated.  
 
No longer do you need to go outside, remove the shoreline cord from the pole and 
plug it into the generator receptacle.  Likewise in marine applications you simply 
start the generator and the 

ATS501

 will switch the loads for you. 

 

OPERATION 
 

After the ATS 501 is installed using one of the typical installations shown in this 
manual, it will be ready for years of trouble free service. Operation is automatic and 
is maintenance free. 

FROM SHORELINE: 

To operate appliances from shoreline power, simply plug in the shoreline cord to the 
power pole at the campground or dock. The 

ATS 501

 automatically connects all AC 

Appliances to shoreline power. 
 

FROM GENERATOR: 

To operate appliances from on board generator simply start the generator. 
After a typical 20 second delay to allow the generator to stabilize the ATS 501 will 
engage, transferring all 120 or 240-volt appliances connected to the ATS 501 load 
terminals to the generator. 
 

AUXILIARY CONTACT OPERATION 
 

The 

ATS

 

501

 RV line generator switch when connected as in the typical installation 

II 

shown in this manual may control other equipment in your vehicle. The auxiliary 

contacts are rated for 30 A @ 120 VAC operation and will switch other loads as the 

ATS 501 

switches from shore power to generator. These contacts are supplied as 

non-energized dry contacts. 
 
 

MOUNTING LOCATION 

 
The 

ATS 501 

series

 

may be installed in any position, leaving room for routing 

shoreline, generator and load conductors. To minimize voltage drop in the wiring the 
transfer switch should be located as close to the generator and shoreline cord entrance 
as practical. 
 

DO NOT 

install the 

ATS 501

 series in the generator compartment.  

 
The 

ATS 501 series is not ignition protected 

and should not be mounted in the same 

compartment as batteries or flammable materials such as gasoline. It may be mounted 
in the cabin or living area or a basement compartment, but is not suitable for outside 
locations. 
 
The 

ATS 501 

should be installed by a qualified electrician. 

 

Typical Installations 

 

 

 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

                           Typical Installations

Rated - 50A 120/240 Volts 60Hz, Neutral rated 70A with jumpers installed.

                                               INSTALLATION  I

 LOAD

    L2

    L2

** Note: Circuit1 and Circuit 2 in phase.

INSTALLATION  II

    L1  

120 VAC

30 A - SHORE

   NEUT.

LOAD

LINE POWER

L1

              C

    DRY AUX.

                 NC

   CONTACTS.
   RATED 30A

                 NO

120 VAC

NEUTRAL

       

         

      ATS 501

     With  jumpers installed.

120 / 240
 50 A - SHORE
  LINE  POWER 

   L1

   NEUT.

 

 120 VAC

 2 CIRCUIT

    GENERATOR

   
** Circuit 1
120 VAC - 35 A Max.

   
** Circuit 2
120 VAC - 35 A Max.

     Neutral rated
       70 A Max.

              

 ATS 501

      

120 VAC

       30 A - Max.
      GENERATOR 

   L1

   NEUT.