background image

   English

3 / 12

ATT025-040     

It is recommended to complete this type of starting with the air out-

let valve closed, to preserve the correct operation of the desiccant bed.

4.3 Operation

Leave the dryer in working during the period of working of the air com-
pressor.

•  The dryer works automatically, calibrations are not required on the 
fi eld;
•  if there are excessive and unexpected air fl ows, by-pass to avoid 
overloading the dryer.

4.4  Operation with Dew point control

In the case of work loads below the nominal or if you want different dew 
point of -40 ° C, it is possible to work in 

Dew Point Control

. The system 

automatically controls the time of the cycles of operation to obtain and 
maintain the predetermined dew point, with the result of energy saving in 
case of work with partial loads.
Procedure to set “dew point control”.

Press Prg  to enter on main menu 
Using 

Up

 and 

Down

 select

USER SETTINGS”

Press 

Enter

 to confi rm.

- - -Main Menu - - -

START/STOP

USER SETTINGS

SERVICE

INFORMATION

Shows the “User settings menu

- User Settings Menu - 

DRYER SETTINGS

DATE/TIME

BMS

MOISTURE DRAIN

OTHER

LANGUAGE

Using 

Up

 and 

Down

 select

“DRYER SETTINGS”

Press 

Enter

 to confi rm.

- User Settings Menu - 

DRYER SETTINGS

DATE/TIME

BMS

MOISTURE DRAIN

OTHER

LANGUAGE

Using 

Up

 and 

Down

 select

the parameter.
Press 

Enter

 to confi rm.

U1 - DEWP.SET (°C):                       -40
U2 - PRESSURE (barg):                   07 
U3 - MODE: Forced Rig.
U4 - ALARM RELAY MODE:
by: ALARMS & WARNINGS

U6 -  DPM:                NO FITTED

Select the parameter 

U1- DEWP.SET

 (°C) and set the value you need. 

Press

 Enter 

to confi rm. see Table 1 for identifying the correct value 

to be set

Select the parameter 

U6- DPM

: set the mode 

FITTED.

 Press

 Enter 

to confi rm.

 

Table 1

Dew
Point

Application

-70°C

Request for a very low dew point.

-40°C

Request for a very low dew point.
(depend on the type of the process.).

-20°C

Request for a low dew point. 
When the pipes air compressed are in external environ-
ment and the minimum winter ambient temperatures are 
above -10 to -15 ° C.

-10°C

Request for a low dew point.
When the pipes air compressed are in external environ-
ment and the minimum winter ambient temperatures are 
above  -5°C.

0°C

Request for a dew point standard.
When the pipes air compressed are in external environ-
ment and the minimum winter ambient temperatures are 
above  10°C.

Important: for correct readings, the Dew point sensor must work at 
a precise air fl ow, which is adjusted by a fl ow meter (no. 33).
CORRECT CALIBRATION: LEVEL    2 ÷ 5     liters/minutes
To ensure optimal Dew point  sensor operation, comply with the 
maintenance instructions given in para. 6.4. 
In this regard, the sensor connection is fi tted with a shut-off valve to 
facilitate maintenance

4.5 Stop

It is possible to stop the dryer in two different mode: 

• NORMAL 
• FORCED

Y

 Is recommended to use the option “Normal”.

Use the option “Forced” only if necessary.

Mode stop “NORMAL”:

Press 

 

to enter on “Main Menu”

- - -Main Menu - - -

START/STOP

USER SETTINGS

SERVICE

INFORMATION

Select 

START/STOP

 

press 

Enter 

to confi rm

- - -Main Menu - - -

START/STOP

USER SETTINGS

SERVICE

INFORMATION

Select 

NORMAL START/STOP

 

press 

Enter 

to confi rm

- On/Off Menu -

NORMAL START/STOP

STOP DIRECTLY

Press 

Enter 

to confi rm the  

STOP

ENABLE UNIT RUNNING

STOP

Y

 

IMPORTANT: wait for the dryer to perform the complete cycle 

of regeneration, IT IS ABSOLUTELY PROHIBITED TO STOP THE 
FLOW OF AIR UNTIL THE STOP OF THE DRYER.
Mode stop “FORCED”. 

Press 

 

to enter on “Main Menu”

- - -Main Menu - - -

START/STOP

USER SETTINGS

SERVICE

INFORMATION

Select 

START/STOP

 

press 

Enter 

to confi rm

- - -Main Menu - - -

START/STOP

USER SETTINGS

SERVICE

INFORMATION

Select

 “Stop Directly”

Press 

Enter 

to confi rm

- On/Off Menu -

NORMAL START/STOP

STOP DIRECTLY

Select 

YES 

and confi rm.

After few second the value return 
to “

NO”

.

FORCING SYSTEM OFF

NO

IMPORTANT: 

Machine ON: the machine should always work under pressure.
Machine OFF: do not allow air to fl ow into the tanks with the dessi-
cant when the machine is turned off.

Summary of Contents for ATT025

Page 1: ...IT Manuale d uso EN User Manual ES Manual de uso DE Benutzer Handbuch ATT025 ATT040 DATE 10 06 2017 Rev 22 CODE 398H272988 ATT 50Hz Antares Tandem Dryer...

Page 2: ......

Page 3: ...dotto e comunque in modo che non venga generata alcuna situazione di rischio I rischi che non stato possibile eliminare in fase di progettazione sono riportati nella tabella seguente Parte Considerata...

Page 4: ...terruttore sezionatore del dryer 3 5 Collegamento scarico condensa Y L essiccatore pu essere dotato di scaricatore a galleggiante tem porizzato o elettronico a sensore di livello In presenza di scaric...

Page 5: ...aria spinta Dew point richiesto da applicazione verniciatura farma ceutica processo 20 C Media qualit aria Impostare questo dew point se la tubazione aria compres sa passa all esterno e le temperature...

Page 6: ...rvento sull essiccato depressurizzare l impianto NON MODIFICARE IN NESSUN CASO LE IMPOSTAZIONI PREDE FINITE DELLA SCHEDA ELETTRONICA DI CONTROLLO 5 Controllo 5 1 Pannello di controllo 5 1 1 Display 5...

Page 7: ...lezionano gli indirizzi per la supervisione Premere esc per tornare a USER SETTINGS MENU Selezionare MOISTURE DRAIN User Settings Menu DRYER SETTINGS DATE TIME BMS MOISTURE DRAIN OTHER LANGUAGE Compar...

Page 8: ...y NO U14 Money Euro U15 Money KWh 0 120 U16 Saving Compared to Heatless U2 2 Parametro U12 Enable Money per abilitare la visualizzazione del risparmio energetico in termini monetari porre a YES 3 Para...

Page 9: ...iuti in garanzia Y L apparecchiatura contiene gas fluorurati a effetto serra Il fluido frigorigeno R134a a temperatura e pressione normale un gas incolore appartenente al SAFETY GROUP A1 EN378 fluido...

Page 10: ...pianto dall aria compressa del dryer 2 Assicurarsi che la pressione sia 0 bar verificando i manometri dei serbatoi ingresso aria n 20 Attenzione il dryer ancora in pressione nella zona di uscita aria...

Page 11: ...N Attivo A06 WARNING PROBE Compres sor DischargeTemperature NU X A 3 s AIN sonda sullo scarico compressore non funzionate S N Attivo A07 WARNING PROBE Thermal MassTemperature NU X A 3 s AIN sonda tem...

Page 12: ...rico compressore S N Attivo A20 WARNING ADSORBER Low Pressure Column 1 X X X A 120s DIN bassa pressione pressostato A N N Attivo A21 WARNING ADSORBER High Pressure Column 1 X X X A 120s DIN alta press...

Page 13: ...del by pass Se entro 2 minuti non apre completamente si verifica l allarme N SI rimane in configurazione WINTER Attivo A35 BYPASS ALARM Fail Close X X 2min Se la configurazione INVERNO il rel eccitato...

Page 14: ...sore No Si Mancanza di refrig erante Si Pulire il condensatore Elevata perdita di carico Scambiatore intasato No Filtri intasati No Formazione ghiaccio No Si Pulire lo scambia tore e sostituire prefil...

Page 15: ...ust be performed in accordance with the information and instructions given in the technical documentation supplied and always in such a way to avoid the creation of a hazardous situation The risks tha...

Page 16: ...supplied either with a float drain a timed drain or an electronic level sensing drain If a timed or electronic unloader is installed use terminals CN R1 S1 see par 9 8 For timed and electronic drains...

Page 17: ...s air compressed are in external environ ment and the minimum winter ambient temperatures are above 10 to 15 C 10 C Request for a low dew point When the pipes air compressed are in external environ me...

Page 18: ...O NOT CHANGE THE DEFAULT OF ELECTRONIC CONTROL CARD 5 Control 5 1 Control panel 5 1 1 Display 5 1 2 Keys KEY PHOTO FUNCTION UP Shifts the cursor or increases the value of a parameter DOWN Shifts the c...

Page 19: ...RE DRAIN User Settings Menu DRYER SETTINGS DATE TIME BMS MOISTURE DRAIN OTHER LANGUAGE This Screen appears MOISTURE DRAIN U9 MODE Continue U10 TIMED On s U11 TIMED Off s 1 U9 Mode condensate drain con...

Page 20: ...g with money change in YES and press enter to confirm 3 Parameter U13 Money choose the money symbol Symbols available Parameter Description Simbol Euro euro USA Dollar U S dollar ENG Pound English pou...

Page 21: ...will not be covered by the warranty 6 2 Refrigerant YCharging any damage caused by incorrect refrigerant replacement carried out by unauthorized personnel will not be covered by the war ranty Y The e...

Page 22: ...wing action 1 Depressurize the compressed air system 2 Make sure that the pressure on both gauges 0 bar AIR IN n 20 Warning the dryer is still under pressure in the AIR OUTLET SIDE of the cooler 3 Dep...

Page 23: ...ve A06 WARNING PROBE Compres sor DischargeTemperature Nu X A 3 s AIN Compressor Discharge Temperature Y N Active A07 WARNING PROBE Thermal MassTemperature Nu X A 3 s AIN Thermal Mass Temperature PROBE...

Page 24: ...r Discharge Temperature Y N Active A20 WARNING ADSORBER Low Pressure Column 1 X X X A 120s DIN Air Pressure Switch A N N Active A21 WARNING ADSORBER High Pressure Column 1 X X X A 120s DIN Air Pressur...

Page 25: ...f the bypass If within 2 minutes does not fall on the end of opening stroke occurs the alarm N Yes remanins in operation WINTER Active A35 BYPASS ALARM Fail Close X X 2min If the operation is WINTER t...

Page 26: ...eteriorated No Yes low level refrigerant Yes Clean the condenser High pressure drop Exchanger dirty No Filters dirty No Formazione ghiaccio No Yes Clean the exchenger and substitute the pre filter Yes...

Page 27: ...pre evitando la generaci n de situaciones peligrosas En la siguiente tabla se recogen los riesgos que no se hayan podido eliminar en la fase de dise o Pieza afec tada Riesgo residual Forma de exposi c...

Page 28: ...Conexi n de descarga del vapor condensado Y El secador es suministrado bien con una purga de flotador bien una purga con temporizador o bien una purga con detecci n electr nica del nivel Si se instala...

Page 29: ...icitud de un punto de roc o bajo Cuando las tuber as de aire comprimido est n en un en torno externo y las temperaturas ambientales m nimas en invierno son superiores a 10 a 15 C 10 C Solicitud de un...

Page 30: ...CI N POR DEFECTO DE LA TARJETA ELECTR NICA DE CONTROL 5 Control 5 1 Panel de Control 5 1 1 Pantalla 5 1 2 Teclas TECLA FOTO FUNCI N UP Cambia el cursor o aumenta el valor del par metro DOWN Cambia el...

Page 31: ...Aparece esta pantalla BMS U7 ADRESS 001 U8 BAUDRATE 9600 Los par metros U7 y U8 seleccionan la direcci n de la supervisi n pulse esc para volver al men USER SETTINGS Seleccione MOISTURE DRAIN User Se...

Page 32: ...NO U13 Enable Money NO U14 Money Euro U15 Money KWh 0 120 U16 Saving Compared to Heatless U2 2 Par metro U12 Enable Money para activar el modo ahorro de energ a viendo el dinero seleccione YES y pulse...

Page 33: ...ci n de la actividad Intervalo de manteni miento condiciones de funcionamiento est n dar Actividad Control Servicio Diario Semanal 4 Meses 12 Meses 24 Meses 48 Meses Compruebe que este encendido el in...

Page 34: ...poliestireno sintetizado aislamiento de la tuber a goma sint tica compresor acero cobre aluminio aceite condensador acero cobre aluminio Refrigerante R134a V lvulas lat n cables el ctricos cobre PVC r...

Page 35: ...o Defectuoso N N Activo A06 WARNING PROBE Compres sor DischargeTemperature Nu X A 3 s AIN Temperatura de descarga del compresor S N Activo A07 WARNING PROBE Thermal MassTemperature Nu X A 3 s AIN PROB...

Page 36: ...arga del compresor S N Activo A20 WARNING ADSORBER Low Pressure Column 1 X X X A 120s DIN Interruptor de Presi n del Aire A N N Activo A21 WARNING ADSORBER High Pressure Column 1 X X X A 120s DIN Inte...

Page 37: ...per tura del bypass Si en 2 minutos no se abre salta la alarma N SI permanece en funcio namiento INVIERNO Activo A35 BYPASS ALARM Fail Close X X 2min Si funciona en INVIERNO el rel es desenergizado pa...

Page 38: ...l com presor deteriorados No S Nivel bajo refrigerante S Limpie el conden sador Ca da de la alta presi n Intercambiador sucio No Filtros sucios No Formaci n de hielo No S Limpie el inter cambiador y c...

Page 39: ...d die Anweisungen in den technischen Ger teunterlagen strikt einzuhalten in jedem Fall ist jedes Vorgehen zu vermeiden dass zu ei ner Gefahrensituation f hrt Die Restrisiken die beim Bau der Maschine...

Page 40: ...Anschluss des Kondensatablaufs Y Der Trockner kann mit einem Ablauf mit Schwimmer mit Zeitsteue rung oder mit elektronischem F llstand ausgestattet werden Falls ein zeitgesteuerter oder elektronischer...

Page 41: ...ie Betriebsart FITTED einstel len Mit Enter best tigen Tabelle 1 Tau punkt Anwendung 70 C Anforderung sehr hoher Luftqualit t F r die Anwendung erforderlicher Taupunkt 40 C Anforderung hoher Luftquali...

Page 42: ...ELECTION English 4 7 Warnungen w hrend der Inbetriebnahme und des Betriebs W hrend der Ausdehnung wird die Luft vom Schalld mpfer aus gesto en das Ger t befindet sich in der Generations Phase Gef hrdu...

Page 43: ...unktregelung Fitted oder mit Zeitsteuerung No Fitted gearbeitet wird Nach der Parameter nderung mit ENTER best tigen Weitere abrufbare Masken dieses Abschnitts sind die folgenden Taste Esc dr cken um...

Page 44: ...arten kWh hervorgeht Dieser Wert wird in der Maske angegeben ENERGY SAVING 000000009 Um diese Maske abzurufen in der Hauptmaske zweimal die Taste DOWN dr cken Die Maske wie folgt aktivieren 1 In PRG U...

Page 45: ...tes Personal werden keine Garantieanspr che anerkannt Y Das Ger t enth lt vom Kyoto Protokoll erfasste fluorierte Treibhausgase Das K ltemittel R134a ist bei Normaltemperatur und druck ein farbloses G...

Page 46: ...en Sie das Druckluftsystem des Trockners drucklos 2 Pr fen Sie an den Beh lter Manometern Lufteinlass Nr 20 ob der Druck 0 bar betr gt Achtung Der Trockner steht im Luftauslassbereich des K hlers noch...

Page 47: ...rature 2 X X X A 3 s AIN Austrittstemperatur F hler Widerstand 2 defekt N N Aktiv A06 WARNING PROBE Compres sor DischargeTemperature Nu X A 3 s AIN F hler am Kompressorauslass defekt J N Aktiv A07 WAR...

Page 48: ...charge Temperature Nu X A Sofort AIN hohe Temperatur am Kompressorauslass J N Aktiv A20 WARNING ADSORBER Low Pres sure Column 1 X X X A 120s DIN Niederdruck Druckschalter A N N Aktiv A21 WARNING ADSOR...

Page 49: ...des By pass angezogen Erfolgt innerhalb von 2 Minuten keine komplette ffnung wird der Alarm ausgel st N JA bleibt auf Konfiguration WINTER Aktiv A35 BYPASS ALARM Fail Close X X 2min Bei Konfiguration...

Page 50: ...digt Nein Ja K ltemittel unzureichend Ja Den Kondensator rei nigen Hohe Druckverluste W rmetauscher verstopft Nein Filter verstopft Nein Eisbildung Nein Ja W rmetauscher reinigen und Vorfilter ersetz...

Page 51: ......

Page 52: ...co MI Italy Sede Operativa Gas Separation and Filtration Division EMEA Strada Zona Industriale 4 35020 S Angelo di Piove PD Italy tel 39 049 971 2111 fax 39 049 9701911 Web site www parker com hzd e m...

Reviews: