English
5 / 12
ATT025-040
5.3.2 USER PARAMETER
Press the key Prg and enter on
MAIN MENU
- - -Main Menu - - -
START/STOP
USER SETTINGS
SERVICE
INFORMATION
Select
USER SETTINGS,
press
Enter
to confi rm
.
Shows the “user setting menu”:
- User Settings Menu -
DRYER SETTINGS
DATE/TIME
BMS
MOISTURE DRAIN
OTHER
LANGUAGE
Select
DRYER SETTINGS
press
Enter
to confi rm. This Screen appears
U1 - DEWP.SET (°C): -40
U2 - PRESSURE (barg): 07
U3 - MODE: Forced Rig.
U4 - ALARM RELAY MODE:
by: ALARMS & WARNINGS
U6 - DPM: NO FITTED
With the keys
Up
,
Down
and
Enter
you can select/change a parameter:
U1 -
SET
of Dew Point
U2 -Work pressure [barg]
U3 - Working Mode: Forced Rig. O Normal
U4 - Alarm Relay Mode by: alarms&warnings or allarms.
U6 -
DPM
: Fitted o No Fitted - with the control fo the dew point (Fitted)
or with fi xed time (No Fitted)
When you change the parameter press
Enter
to confi rm.
Press
Esc
to return on
USER SETTINGS MENU
.
Select
DATE
for change the date and the time:
- User Settings Menu -
DRYER SETTINGS
DATE/TIME
BMS
MOISTURE DRAIN
OTHER
LANGUAGE
This Screen appears:
2011/Oct/24 15.49
Change: NO
M10
Press esc to return on
USER SETTINGS MENU
.
Select
BMS
:
- User Settings Menu -
DRYER SETTINGS
DATE/TIME
BMS
MOISTURE DRAIN
OTHER
LANGUAGE
This Screen appears:
- BMS -
U7 - ADRESS: 001
U8 - BAUDRATE: 9600
The parameters
U7
and
U8
selects the adress fo the supervision.
Press esc to return on the
USER SETTINGS MENU
.
Select
MOISTURE DRAIN:
- User Settings Menu -
DRYER SETTINGS
DATE/TIME
BMS
MOISTURE DRAIN
OTHER
LANGUAGE
This Screen appears:
- MOISTURE DRAIN -
U9 - MODE: Continue
U10 - TIMED On (s):
U11 - TIMED Off (s): 1
U9 - Mode condensate drain (continue; timed; capacitive);
U10 - Time “ON” with timed condensate drain;
U11 - Time “OFF” with timed condensate drain;
Press
Esc
to return on
USER SETTINGS MENU
.
Select
OTHER
:
- User Settings Menu -
DRYER SETTINGS
DATE/TIME
BMS
MOISTURE DRAIN
OTHER
LANGUAGE
This Screen appears:
U12 - BACKLIGHT ON: NO
U13 - Enable Money : NO
U14 - Money : Euro
U15 - Money / KWh : 0.120
U16 - Saving Compared
to Heatless
U2
5.3.3 SERVICE PARAMETER
On
MAIN MENU
select
Service
and press
Enter
to confi rm.
- - -Main Menu - - -
START/STOP
USER SETTINGS
SERVICE
INFORMATION
This Screen appears with the request of a password.
INSERT PASSWORD
000
These confi guration parameters must not be editable by the customer.
5.3.4 INFORMATIONS
On
MAIN MENU
select
INFORMATION
and press
Enter
to confi rm.
- - -Main Menu - - -
START/STOP
USER SETTINGS
SERVICE
INFORMATION
From this page you can view system information and alarm history.
Select
SYSTEM INFO
and press
Enter
to confi rm:
- - - Informations Menu - - -
SYSTEM INFO
ALARMS HISTORICAL
Using
Up
and
Down
. You can view:
-
Information on cycles times;
’
-
Values input signals:
INPUTS
Pressure 1 (B6) : 04.2
Pressure 1 (B7) : 04.3
Level (B8) : NO WAT:
AD Inlet Temp (B9): 02.6
Thermal Mass (B10): 02.4
- Counter
2014/Gen/24 16.20.20
HOURS COUNTERS
UNIT_ON : 000001 (h)
COMPRESSOR : 000001 (h)
LAST OFF DAY : 00,00.00
S1
-
Information about software
SOFTWARE INFO
SW Release : 10
SW date: 2014/01/20
Bios : 5.00. 20/May/01
Boot : 4.00. 20/May/01