English
2/6
2 Introduction
Th
ese water coolers are monoblock units for the production of cooled
water in a closed circuit.
Th
e fan, pump and compressor motors are equipped with a thermal
protector that protects them against possible overheating.
2.1 Transport
Th
e packed unit must remain:
a) Upright;
b) Protected against atmospheric agents;
c) Protected against impacts.
2.2 Handling
Use a fork-lift truck suitable for the weight to be lift ed, avoiding any
type of impact
2.3 Inspection
a) All the units are assembled, wired, charged with refrigerant and oil
and tested in the factory;
b) On receiving the machine check its condition: immediately notify
the transport company in case of any damage;
c) Unpack the unit as close as possible to the place of installation.
2.4 Storage
a) Keep the unit packed in a clean place protected from damp and bad
weather.
b) Do not stack the units;
c) Follow the instructions given on the package.
3 Installation
Y
For correct installation, follow the instructions given in par.7.1
and 7.2.
!
Liquids to be chilled
Th
e liquids to be chilled must be compatible with the materials used.
Examples of liquids used are water or mixtures of
water and ethylene
or propylene glycols.
Th
e liquids to be chilled must not be fl ammable.
If the liquids to be chilled contain hazardous substances (e.g. ethylene/
propylene glycol), any liquid discharged from a leakage area must be
collected, because it is harmful to the environment. When draining
the hydraulic circuit, comply with the current regulations and do not
disperse the contents in the environment.
3.1 Operating
space
Leave a space of 1.5 m around the unit.
Leave a space of at least 2 metres above the refrigerator in models with
vertical emission of condensation air.
3.2 Versions
Axial fans (A)
Do not create cooling air recirculation situations.
Do not obstruct the ventilation grilles.
Th
e ducting of extracted air is not recommended for versions with
axial fans.
3.3 Water
circuit
3.3.1
Checks and connection
Y
Before connecting the chiller and fi lling the water circuit, check
that all the pipes are clean. If not, wash them out thoroughly.
Y
If the plumbing circuit is of the closed type, under pressure it is
advisable to install a safety valve set to 6 bar.
Y
Always install mesh fi lters on the water inlet and outlet pipelines.
Y
If the hydraulic circuit is intercepted by automatic valves, protect
the pump with an anti-hammering system.
Y
If the hydraulic circuit is emptied for shut-down periods we
recommend that you add lubricating fl uid to the pump’s impeller to
avoid the risk of blockage when it is re-started. In case the impeller is
blocked then you should unblock it manually.
Remove the rear cover of the pump and carefully turn the plastic fan.
If the impeller is stuck then remove the fan and turn the impeller shaft
directly. Aft er un-blocking the impeller re-assemble the fan and
cover.
Preliminary checks
1) Check that any shut-off valves in the water circuit are open.
2) In the case of a closed water circuit, check that an expansion tank
of suitable capacity has been installed. See paragraph 3.3.3..
Connection
1) Connect the water cooler to the inlet and outlet piping, using the
special connections located on the back of the unit.
We recommend the use of fl exible unions to reduce system rigidity.
2) Fill the water circuit using the fi tting provided on the rear of the
chiller (
).
3) Th
e tank is equipped with a breather valve that should be operated
manually when fi lling the tank. Also, if the hydraulic circuit has high
points, install a vent valve at the highest points.
4) We recommend that taps are installed on the inlet and outlet pipes,
so that the unit can be excluded for maintenance when necessary.
5) If the chiller works with an open tank, the pump must be installed
on intake to the tank and on delivery to the chiller.
Subsequent checks
1) Check that the tank and the circuit are completely full of water and
that all the air has been expelled from the system.
2) Th
e water circuit must always be kept full. For this reason, carry
out periodic checks and top the circuit up if necessary, or install an
automatic fi lling kit.
3.3.2
Water and ethylene glycol
If installed outdoors or in an unheated indoor area, it is possible that
the water in the circuit may freeze if the system is not in operation dur-
ing the coldest times of the year.
To avoid this hazard:
a) Equip the chiller with suitable antifreeze protection devices, avail-
able from the manufacturer as optional accessories;
b) Drain the system via the drain valve if the chiller is to remain idle
for a prolonged period;
c) Add an appropriate quantity of antifreeze to the water in circula-
tion (see table).
Sometimes the temperature of the outlet water is so low as to require
the addition of ethylene glycol in the following percentages.
Outlet water
temperature [°C]
Ethylene glycol
(% vol.)
Ambient
temperature
4
5
-2
2
10
-5
0
15
-7
-2
20
-10
-4
25
-12
-6
30
-15
3.3.3 Expansion
tank
To avoid the possibility of an increase or decrease in the volume of the
fl uid due to a signifi cant change in its temperature causing damage to
the machine or the water circuit, we recommend installing an expan-
sion tank of suitable capacity.
Th
e expansion tank must be installed on intake to the pump on the rear
connection of the tank.
Th
e minimum volume of an expansion tank to be installed on a closed
circuit can be calculated using the following formula:
V=2 x Vtot x (Pt min - P t max)
where
Vtot= vol. circuit total (in litres)
P t min/max= specifi c weight at the minimum/maximum temperature
reached by the water [kg/dm3].
Th
e specifi c weight values at diff erent temperatures for glycol percent-
age values are given in the table.
%
glicol
Temperature [°C]
-10
0
10
20
30
40
50
0%
1.0024 1.0008 0.9988 0.9964 0.9936 0.9905 0.9869
10%
1.0177 1.0155 1.0130 1.0101 1.0067 1.0030 0.9989
ICE007-010