Hyperchill-Precision Control ICE015-057
5 Maintenance
a) Th
e machine is designed and built to guarantee continuous opera-
tion; however, the life of its components depends on the mainte-
nance performed.
b) When requesting assistance or spare parts, identify the machine
(model and serial number) by reading the dataplate located on the
unit.
c) Circuits containing 3 kg or more of refrigerant fl uid are checked to
identify leaks at least once a year.
Circuits containing 30 kg or more of refrigerant fl uid are checked to
identify leaks at least once every six months. ((EU) No. 517/2014 art.
4.3.a, 4.3.b).
d) For machines containing 3 kg or more of refrigerant fl uid, the op-
erator must keep a record stating the quantity and type of refrigerant
used, an quantities added and that recovered during maintenance
operations, repairs and fi nal disposal ((EU) No. 517/2014 art. 6). An
example of this record sheet can be downloaded from the site: www.
polewr.com.
5.1 General instructions
!
Before performing any maintenance, make sure the power to the
refrigerator is disconnected.
Y
Always use the Manufacturer’s original spare parts: otherwise the
Manufacturer is relieved of all liability regarding machine malfunction-
ing.
Y
In case of refrigerant leakage, contact qualifi ed and authorized
personnel.
Y
Th
e Schrader valve must only be used in case of machine malfunc-
tion: otherwise any damage caused by incorrect refrigerant charging
will not be covered by the warranty.
5.2 Preventive maintenance
To guarantee lasting maximum chiller effi
ciency and reliability, carry
out:
a)
Z
every 4 months -
clean the condenser fi ns and make sure com-
pressor electrical absorption is within the dataplate values;
b)
Z
yearly - W
version: in case of encrustations inside the con-
denser, introduce and circulate a specifi c detergent liquid.
b)
Z
Every 3 years -
installation of kit for maintenance every 3
years. (par.7.5)
a)
kit for maintenance every 3 years;
b)
service kit;
1. compressor
kit;
2. fan
kit;
3.
P3 pump kit;
4.
expansion valve kit
c)
individual spare parts.
5.3 Refrigerant
Z
Charging: any damage caused by incorrect charging carried out by
unauthorized personnel will not be covered by the warranty.
Y
Th
e equipment contains fl uorinated greenhouse gases.
At normal temperature and pressure, the R407C refrigerant is a col-
ourless gas classifi ed in SAFETY GROUP A1 - EN378 (group 2 fl uid
according to Directive PED 97/23/EC);
GWP (Global Warming Potential) = 1774.
!
In case of refrigerant leakage, air the room.
5.4 Dismantling
Th
e refrigerant and the lubricating oil contained in the circuit must be
recovered in conformity with current local environmental regulations.
Th
e refrigerant fl uid is recovered before fi nal scrapping of the equip-
ment ((EU) No. 517/2014 art.8).
%
Recycling
Disposal
frame and panels
steel/epoxy resin polyester
tank
aluminium/copper/steel
pipes/collectors
copper/aluminium/carbon steel
pipe insulation
NBR rubber
compressor
steel/copper/aluminium/oil
condensator
steel/copper/aluminium
pump
steel/cast iron/brass
fan
aluminium
refrigerant
R407C (HFC)
valve
brass/copper
electrical cable
copper/PVC
Summary of Contents for Hyperchill ICE015
Page 2: ......
Page 10: ...Italiano 8 8 Hyperchill Precision Control ICE015 057 ...
Page 18: ...English 8 8 Hyperchill Precision Control ICE015 057 ...
Page 26: ...Español 8 8 Hyperchill Precision Control ICE015 057 ...
Page 34: ...Deutsch 8 8 Hyperchill Precision Control ICE015 057 ...
Page 35: ......