   ICE150-230

4.4.1.2 

Alarm relay management

0

Relay normally deactivated, excited by an alarm.

1

Relay normally excited (also with control OFF), deactivated 
by an alarm.

2

Relay normally excited (only with control ON), deactivated 
by an alarm or with control OFF.

4.4.2 Temperature 

control

PARAMETER

CODE

TYPE

DEFAULT

Temperature control set point

SEt

D

--

Temperature control differential

dIF

D

4.0

Set point lower limit

LI5

U

5.0

4.4.3 

B1 sensor parameters

PARAMETER

CODE

TYPE

DEFAULT

High temperature confi guration

cHAI

U

0

High temperature alarm

HAI

D

60.0

Low temperature alarm

LAI

D

-20.0

Sensor calibration

CAI

U

0.0

Low temperature alarm reset
differential

dbI

U

1.0

4.4.4 

B2 sensor parameters

PARAMETER

CODE

TYPE

DEFAULT

High temperature confi guration

cHA2

U

0

High temperature alarm

HA2

U

60.0

Low temperature alarm

LA2

U

3.0

Sensor calibration

CA2

U

0.0

B2 sensor presence

Ab2

U

1.0

4.4.5 

B3 sensors parameters

PARAMETER

CODE

TYPE

DEFAULT

High temperature alarm

HA3

U

60.0

Low temperature alarm

LA3

U

-20.0

Sensor calibration

CA3

U

0.0

4.4.6 

B5 sensors parameters

PARAMETER

CODE

TYPE

DEFAULT

High temperature alarm

HA5

U

60.0

Low temperature alarm

LA5

U

-20.0

Sensor calibration

CA5

U

0.0

4.4.7 

B7 sensor parameters

PARAMETER

CODE

TYPE

DEFAULT

High temperature confi guration

cHA7

U

0

High temperature alarm

HA7

U

60.0

Low temperature alarm

LA7

U

3.0

Sensor calibration

CA7

U

0.0

B7 sensor presence

Ab7

U

1.0

4.4.8 Compressor 

parameters

PARAMETER

CODE

TYPE

DEFAULT

Compressor rotation

rot

U

2

Compressor 1 operation hour 
counter

HI

D

-

Compressor 3 operation hour 
counter

H3

D

-

Compressor 2 operation hour 
counter

H2

D

-

Compressor 4 operation hour 
counter

H4

D

-

Compressor 1 hour counter 
threshold

tHI

U

0

Compressor 3 hour counter 
threshold

tH3

U

0

Compressor 2 hour counter 
threshold

tH2

U

0

Compressor 4 hour counter 
threshold

tH4

U

0

4.4.9 Pump 

parameters

PARAMETER

CODE

TYPE

DEFAULT

Pump stop delay

dP5

U

5

Pump start delay

dPA

U

5

4.4.10 

Antifreeze heater parameters

PARAMETER

CODE

TYPE

DEFAULT

Set point adjustment (B1)

SEA

U

7.0

Temperature control differential (B1)

dIA

U

1.0

Antifreeze heater operating mode
(see para. 4.4.8.1)

FUA

U

0

Antifreeze heater activation mode
(see para. 4.4.8.2)

AbrA

U

2

Activation set point (B3)

ArA

U

5.0

4.4.10.1  FUA antifreeze heater operating mode

0

Temperature control by B1, activation by B3 (ambient
temperature sensor)

1

Temperature control by B3 (ambient temp. sensor) with
ARA set point.

4.4.10.2  AbrA antifreeze heater activation mode

0

Activation only when controller is ‘On’

1

Activation also when controller is ‘Off’

2

Activation also when controller is ‘Off’. During heater opera-
tion the pump is activated.

4.5 Parameter management

4.5.1 

Temperature setting (see fi g.1)

1. 1. Turn the main swicth (QS) to “ON” and wait for the temperature 

visualization.

2. Press buttons “

P3

” and “

P5

” together, to enter into “

dIrE

” (D)

 

parameters.

3. Press button  “

P4

” to select “

SEt

” parameter, press the button 

P5

” to  confi rm.

4.  Change the value, using the up and down arrow buttons “

P3

” and 

P4

”, then press button “

P5

” to confi rm.

6. Press the button “

P3

” to return on “

dIrE

 parameter.

7. Press the button “

P5

” to exit.

4.5.2 

Differential setting (see fi g.1)

1. Turn the main swicth (QS) to “ON” and wait for the temperature 

visualization.

2. Press buttons “

P3

” e “

P5

” together, to enter into “

dIrE

” (D)

 

parameters.

3. Press button two times “

P4

” to select “

diF

” parameter, press the 

button “

P5

” to  confi rm.

4.  Change the value, using the up and down arrow buttons “

P3

” and 

P4

”, then press button “

P5

” to confi rm.

6. Press the button two times “

P3

” to return on “

dIrE

 parameter.

7. Press the button “

P5

” to exit.

4.5.3 

Visualization sensors B1,B2...

“B1” is the “set” sensor of the macchine.

1. Start the chiller.
2. Press the button “

P4

” to visualize the temperature of the next sen-

sor.

3. Press the button “

P5

” to visualize the sensors “

b01

” ..“

b02

”....

It is recommended to leave  on the display the B1 “set” sensor.

Summary of Contents for Hyperchill ICE183

Page 1: ...Hyperchill 50Hz ICE150 ICE183 ICE230 DATE 29 04 2019 Rev 28 CODE 398H271650 IT Manuale d uso EN User Manual ES Manual de uso DE Benutzer Handbuch...

Page 2: ......

Page 3: ...il diritto di modificare le infor mazioni contenute nel presente manuale senza alcun preavviso Ai fini di una completa ed aggiornata informazione si raccomanda all utente di consultare il manuale a b...

Page 4: ...iempire il circuito assicurarsi che le tubazioni siano pulite In caso contrario effettuare un lavaggio accurato Y Se il circuito idraulico di tipo chiuso in pressione consigliabile installare una valv...

Page 5: ...d installazione della macchina La corrente nominale In di tale magnetotermico deve essere uguale a FLA e la curva di intervento di tipo D 5 Valore massimo dell impedenza di rete 0 274 ohm Controlli s...

Page 6: ...con pompa OFF Pmin P1 P0 Pmax Esempio n 1 Condizioni circuito chiuso a pressione P0 di 2 bar dati targa pompa Pmin 1bar Pmax 3bar regolare l uscita valvola per una pressione di 3bar P1 5Bar Esempio n...

Page 7: ...Differenziale termostatazione B1 dIA U 1 0 Modalit funzionamento resisten za antigelo paragrafo 4 4 8 1 FUA U 0 Modalit attivazione resistenza antigelo paragrafo 4 4 8 2 AbrA U 2 Set point attivazione...

Page 8: ...one circuito 2 M 4 6 2 Allarmi da ingressi analogici AI CODICE DESCRIZIONE RESET B1 HAI Allarme alta temperatura uscita acqua serbatoio Avviso LAI Allarme bassa temperatura uscita acqua serbatoio A St...

Page 9: ...la macchina in caso contrario i danni provocati da errata carica di refrigerante non verranno riconosciuti in garanzia 5 2 Manutenzione preventiva Per garantire nel tempo la massima efficienza ed affi...

Page 10: ...ASATO SOSTITUIRE IL FILTRO ALETTE DEL CONDENSATORE SPORCHE PULIRE LE ALETTE DEL CONDENSATORE SUPERFICIE DEL CONDENSATORE OSTRU ITA LIBERARE LA SUPERFICIE FRONTALE DEL CONDENSATORE PORTATA ACQUA INSUFF...

Page 11: ...ves the right to modify this manual at any time For the most comprehensive and updated information the user is advised to consult the manual supplied with the unit 1 4 Residual risks The installation...

Page 12: ...the water inlet and outlet pipelines Y If the hydraulic circuit is intercepted by automatic valves protect the pump with an anti hammering system Y If the hydraulic circuit is emptied for shut down p...

Page 13: ...ck that the machine and the auxiliary equipment are earthed and protected against short circuit and or overload Once the unit has been connected and the upstream main switch closed thereby connecting...

Page 14: ...limit values Pmax and Pmin indicated on the pump data plate P1 pressure with pump ON P0 pressure with pump OFF Pmin P1 P0 Pmax Example n 1 Conditions closed circuit pressure P0 2 bar pump data plate...

Page 15: ...hour counter threshold tH4 U 0 4 4 9 Pump parameters PARAMETER CODE TYPE DEFAULT Pump stop delay dP5 U 5 Pump start delay dPA U 5 4 4 10 Antifreeze heater parameters PARAMETER CODE TYPE DEFAULT Set po...

Page 16: ...analogici AI CODE DESCRIPTION RESET B1 HAI Tank water outlet water high tempera ture alarm Warning LAI Tank water outlet water low tempera ture alarm A StI Sensor open circuit or short circuit M B2 H...

Page 17: ...unction otherwise any damage caused by incorrect refrigerant charg ing will not be covered by the warranty 5 2 Preventive maintenance To guarantee lasting maximum chiller efficiency and reliability ca...

Page 18: ...FILTER CLOGGED RENEW THE FILTER CONDENSER FINS DIRTY CLEAN THE FINS OF THE CONDENSER CONDENSER SURFACES CLOGGED CLEAR THE FRONT SURFACE OF THE CON DENSER INSUFFICIENT WATER FLOW INCREASE THE FLOW RATE...

Page 19: ...abricante se reserva el derecho de modificar sin previo aviso la informaci n de este manual Para que la infor maci n resulte completa se recomienda al usuario consultar el manual a pie de m quina 1 4...

Page 20: ...talar filtros de red en los tubos de entrada y salida del agua Y Si el circuito hidr ulico posee v lvulas autom ticas de corte proteger la bomba con sistemas contra golpe de ariete Y Si se vac a el ci...

Page 21: ...ocircuitos y sobrecargas Una vez conectado el equipo cuando se cierra el interruptor ge neral de alimentaci n para energizarlo la tensi n en el circuito el ctrico alcanza valores peligrosos Se recomie...

Page 22: ...P0 y los valores l mite de presi n Pm x y Pm n indicados en la placa de datos de la bomba P1 presi n con bomba ON P0 presi n con bomba OFF Pm n P1 P0 Pm x Ejemplo n 1 Condiciones circuito cerrado a p...

Page 23: ...compresor 4 tH4 U 0 4 4 9 Par metros de la bomba PAR METRO C DIGO TIPO PREDET Retardo apagado de la bomba dP5 U 5 Retardo encendido bomba dPA U 5 4 4 10 Par metros de la resistencia antihielo PAR MET...

Page 24: ...le circuito 2 M 4 6 2 Alarmas desde las entradas anal gicas AI C DIGO Descripci n Restabl B1 HAI Alarma alta temperatura salida de agua dep sito Avviso LAI Alarma baja temperatura salida de agua dep s...

Page 25: ...el equipo de lo contrario los da os causados por una carga incorrecta de refrigerante no ser n reconocidos en garant a 5 2 Mantenimiento preventivo Para garantizar la m xima eficacia y fiabilidad del...

Page 26: ...TASCADO SUSTITUIR EL FILTRO ALETAS DEL CONDENSADOR SUCIAS LIMPIAR LAS ALETAS DEL CONDENSADOR SUPERFICIE DEL CONDENSADOR OBSTRUIDA LIBERAR LA SUPERFICIE FRONTAL DEL CONDENSADOR CAUDAL DE AGUA INSUFICIE...

Page 27: ...en f r die korrekte bzw in vern nftiger Weise vorhersehbare Nutzung der Anlage bzw der Bauteile ausreichen ACHTUNG Der Hersteller beh lt sich das Recht vor die in dem vorliegenden Handbuch enthaltenen...

Page 28: ...geschlossenem Wasserkreislauf ist die Installation eines 6 Bar geeichten Sicherheitsventiles erforderlich Y Am Wasser Ein und Austritt sollten stets geeignete Siebfilter installiert werden Y Wird der...

Page 29: ...Nennstrom In des Schutzschalters muss FLA entsprechen und die Ausl sekennlinie muss vom Typ D sein 5 Maximaler Netzimpedanzwert 0 274 Ohm Nachfolgende Kontrollen Sicherstellen dass die Einheit und daz...

Page 30: ...en P1 Druck Pumpe ON P0 Druck Pumpe OFF Pmin P1 P0 Pmax Beispiel Nr 1 Bedingungen Geschlossener Kreislauf bei P0 Druck von 2 bar Daten des Pumpenschilds Pmin 1bar Pmax 3bar Den Ventilausgang f r einen...

Page 31: ...AMETER CODE TYP DEFAULT Verz gerung Pumpenstopp dP5 U 5 Verz gerung Pumpenstart dPA U 5 4 4 10 Parameter des Frostschutzwiderstands PARAMETER CODE TYP DEFAULT Sollwert Einstellung B1 SEA U 7 0 Differe...

Page 32: ...en AI CODE Beschreibung R ckstellung B1 HAI Alarm hohe Temperatur am Wassertan kauslauf Warnmeldung LAI Alarm niedrige Temperatur amWasser tankauslauf A StI Sensor ge ffnet oder Kurzschluss im Sensor...

Page 33: ...usetzen anderenfalls werden Sch den infolge unkorrekter K ltemittelbef llung nicht von der Garantie abge deckt 5 2 Vorbeugende Wartung F r eine stets optimale Effizienz und Zuverl ssigkeit des Chiller...

Page 34: ...ER ERSETZEN RIPPEN DES KONDENSATORS VERSCHMUTZT RIPPEN DES KONDENSATORS REINIGEN OBERFL CHE DES KONDENSATORS BEDECKT BEDECKUNG AN FRONTOBERFL CHE DES KONDENSATORS ENTFERNEN WASSER VOLU MENSTROM UNZU R...

Page 35: ......

Page 36: ...co MI Italy Sede Operativa Gas Separation and Filtration Division EMEA Strada Zona Industriale 4 35020 S Angelo di Piove PD Italy tel 39 049 971 2111 fax 39 049 9701911 Web site www parker com hzd e m...

Reviews: