MPS-2 Series Sensor
CVM-102P
2
2
1
4
3
Sensor Pin Out
Pin #
1
Brown: 24VDC
2
White: NPN / PNP Open Collector Output
3
Blue:
0VDC
4
Black: NPN / PNP Open Collector Output
Output Modes
The MPS-2 Series Sensor has two independent NPN or PNP
open collector output signals. The Switch Output Mode has a
switch point programmed by the user at a specified pressure.
The Hysteresis Range
(h)
adjustment controls the output signal
0 to 100% below the Switch Point
(H)
.
The Window Comparator Mode provides two Switchpoint Settings
(A)
and
(b)
that control the output signals (NPN / PNP) between
two pressures. This is referred to as the “High / Low” setting.
h
H
off
off
0
-30 in Hg
on
on
A
b
off
off
off
-30 in. Hg
0
on
on
Switch Output
Window Comparator Output
Operating Pressure Range
(V) Vacuum (0 to -30 inHg)
(R) Compound (-14.7 to +72.5 PSI)
bar:
0.001
bar:
0.01
Units of Measure
kPa:
0.1
kPa:
1
Display Resolution
mmHg:
1
kgf/cm
2
:
0.01
inHg:
0.1
PSI:
0.1
Media
Air and Non-Corrosive Gases
Pressure Port
N
: 1/8" NPT,
R
: 1/8" BSPT,
G
: 1/8" BSPP,
M5:
M5 Female
Proof Pressure
V
: 72.5 PSI,
R
: 116.0 PSI
Operating Temperature
32 to 122°F (0 to 50°C)
Storage Temperature
14 to 140°F (-10 to 60°C)
Humidity
35 to 85% RH
Electrical Connection
C
: 4-Pin, M8 Connector,
G
: 2m Grommet Open Lead
Power Supply
10.8 to 30VDC, Ripple Vp-p 10% Max., Reverse Voltage Protection
Display
3-Digit, 7-Segment LED
Display Refresh
0.1 to 3.0 sec. (Factory set at 0.1)
Output Circuit
NPN (Sinking) or PNP (Sourcing) Output, Open Collector Transistor 30VDC, 125mA
Switch Output
2 Output Signals, NPN or PNP, Normally Open or Closed, LED Indicator
Output Modes
Hysteresis or Window Comparator
Specifications
Brown V+
White
Analog 1 to 5 VDC
Blue 0V
Black
NPN / PNP Output
Lead Wiring