Application ‘5’: PID
A simple application using a Proportional-Integral-Derivative 3-term controller. The setpoint is taken from
AIN1, with feedback signal from the process on AIN2. The scale and offset features of the analogue input
blocks may be used to correctly scale these signals. The difference between these two signals is taken as
the PID error. The output of the PID block is then used as the drive setpoint.
Configuration Setup:
RL1A
110-230Vac (or 24Vdc) voltage supply
RL1B
Healthy:
Relay output (to lamp)
TH1
Motor Thermistor ‘+’ connection
TH2
Motor Thermistor ‘-’ connection
AI1
Process Setpoint (%) – input 1:
0-10V variable input (from potentiometer)
AI2
Process Feedback (%) – input 2:
4-20mA variable input (from current source)
AO1
Speed Demand (%):
0-10V variable output (to voltmeter)
AO2
Value = 100%:
0-10V variable output (+10V fixed reference voltage)
DX1
Run Forward:
24V digital input
DX2
Remote Reverse:
24V digital input
DX3
Jog:
24V digital input
DI4
Not Stop:
24V digital input
DI5
Not Coast Stop:
24V digital input
STO
STO
DISABLED
(drive operational)
V
↑
V
S