16
MSC4000 - MSC15000 USER GUIDE
LOW FREON/OIL PSI
ALARM SHUT DOWN
DEW POINT 35ºF (2ºC)
J1 ALARM LOG
HIGH DEW POINT
DAYS SINCE LAST: 1
ALARM OUT: YES
J2 ALARM LOG
LOW FLOW
DAYS SINCE LAST: 25
ALARM OUT: YES
J3 ALARM LOG
DP PROBE DEFAULT
DAYS SINCE LAST: 365
ALARM OUT: YES
J4 ALARM LOG
MOTOR OVERLOAD
DAYS SINCE LAST: ---
ALARM OUT: YES
ALARM SHUT DOWN
When a “shut-down” alarm occurs, the dryer will “stop
operating and will require a Manual Reset (see VIEW ALARMS section). Once
the alarm has been reset and if the alarm condition has been cleared, the system
may be re-started. The current mode LED will be flashing. When the mode selector
button is depressed, the system will restart and LED will stop flashing and
remain illuminated.
IMPORTANT
All screens from section (d.) forward to the end of this manual are indicated with an alphanumeric indication
in the upper left corner of the display as a screen ID. The CONTR
d. REVIEW ALARM LOG (“J” Series Menus)
-------------------------------------------------------------
When the Review Alarm Log pushbutton is depressed, the “J” series screens will be displayed.
Each “J” screen shows the status of a possible alarm. The UP/DOWN arrow will allow
scrolling through 16 different alarm conditions. The number appearing next the “DAYS
SINCE LAST”, indicated the last time that the alarms condition has occurred. A zero (0)
indicates the current date. For example, 365 would indicate exactly one year since the
occurrence of any particular alarm. If “---“ is indicated, that means the selected alarm
All screens from section (d.) forward to the end of this manual are indicated with an alphanumeric indication
in the upper left corner of the display as a screen ID. The CONTROL CENTER will display these ID’s as
any given screen is selected within the menu tree. Please make note of any particular screen ID when
communicating with a support representatives, which may be in question.
When an alarm is tripped, the “COMMON ALARM RELAY” (K16) will energize if the “ALARM OUT” is
ENABLED. There is a form “C” dry contact available for the user on K16 (see schematic). To “DISABLE”
the ALARM OUT from energizing the Common Alarm relay, use the SET and UP/DOWN arrow buttons to
disable any given alarm. All alarms are factory default to “ENABLED”. The used can program anyone, any
combination, or all alarms to activate the Common Alarm relay.