background image

6

Parker Hannifin Corporation

 Bulletin TI-HFX-3D

Alarms

Figure 6 - Front View, Service Panel Removed

!

Alarm Set Points

4

1

Alarm Relay Contacts

The high and low limits of the alarm may be set anywhere between 0.5% and 25% oxygen,
depending on the process limitations.  To set the high alarm set point, press the alarm set switch
upward and simultaneously adjust the high potentiometer until the display shows the desired high
alarm set point.  To set the low alarm set point, press the alarm set switch downward and simulta-
neously adjust the low potentiometer until the display shows the desired low alarm set point.

The oxygen analyzer also includes high and low alarm relay contacts located inside the service
panel.  The oxygen analyzer, through the use of the alarm relay contacts, may be used to control
the process stream (see Figure 6).  For example, a high or low oxygen concentration could signal
a remote alarm, open a backup supply of the process stream, or close the process down for
protection of downstream equipment or processes.  The alarm relay contacts should be wired by a
qualified electrician.  Both the high and low oxygen alarm conditions are provided with three relay
outputs:  a common (C), a normally open (NO), and normally closed (NC).

To eliminate the possibility of electrical shock, disconnect the power cord before wiring the

To eliminate the possibility of electrical shock, disconnect the power cord before wiring the

To eliminate the possibility of electrical shock, disconnect the power cord before wiring the

To eliminate the possibility of electrical shock, disconnect the power cord before wiring the

To eliminate the possibility of electrical shock, disconnect the power cord before wiring the
alarm relay contacts to outside circuitry.

alarm relay contacts to outside circuitry.

alarm relay contacts to outside circuitry.

alarm relay contacts to outside circuitry.

alarm relay contacts to outside circuitry.

The relay contacts are rated for 250 VAC, 5 amps resistive or 3 amps inductive load or

The relay contacts are rated for 250 VAC, 5 amps resistive or 3 amps inductive load or

The relay contacts are rated for 250 VAC, 5 amps resistive or 3 amps inductive load or

The relay contacts are rated for 250 VAC, 5 amps resistive or 3 amps inductive load or

The relay contacts are rated for 250 VAC, 5 amps resistive or 3 amps inductive load or
24 VDC 5 amps resistive or 3 amps inductive load.  Do not exceed these values in order to

24 VDC 5 amps resistive or 3 amps inductive load.  Do not exceed these values in order to

24 VDC 5 amps resistive or 3 amps inductive load.  Do not exceed these values in order to

24 VDC 5 amps resistive or 3 amps inductive load.  Do not exceed these values in order to

24 VDC 5 amps resistive or 3 amps inductive load.  Do not exceed these values in order to
maintain the instrument safety certification.

maintain the instrument safety certification.

maintain the instrument safety certification.

maintain the instrument safety certification.

maintain the instrument safety certification.

The customer is responsible for the circuitry utilizing these relay outputs and should use good
engineering safety practices in the design of this circuitry.

1

1

1

1

1

Strip all connecting wires to 1/4" to 3/8" (6mm to 9mm) using wire strippers.

2

2

2

2

2

Insert small screwdriver into the hole below the wire connection point and press to open
connector.

3

3

3

3

3

Slide the stripped wire end into the connection port until it “bottoms out”.

4

4

4

4

4

Remove the screwdriver to clamp the wire into the connection port.  Pull the wire gently to test
integrity of the connection.  Repeat this procedure from step 2 if the wires release easily.

5

Thread wires through electrical access opening on right side of generator (see Figure 1).

Summary of Contents for Balston HFX-3

Page 1: ...separate air into a concentrated nitrogen output stream and an oxygen enriched permeate stream To monitor the purity of the nitrogen stream Parker has incorporated an oxygen analyzer into the design o...

Page 2: ...ure 1 Air separation takes place in the membrane module This module consists of bundles of hollow fiber membranes The compressed air enters the center bore of these fibers and travels the length of th...

Page 3: ...junction with safety interlocks and or alarm systems to assure proper nitrogen purity levels at all times systems to assure proper nitrogen purity levels at all times systems to assure proper nitrogen...

Page 4: ...nt surrounding the nitrogen generator should also be adequately ventilated The environment surrounding the nitrogen generator should also be adequately ventilated The generator creates a 30 to 40 oxyg...

Page 5: ...sure to maintain the proper polarity black red The HFX0 3 Nitrogen Generator is preset at the factory for operation at 120 VAC The voltage setting for the generator is shown through a small window on...

Page 6: ...outside circuitry alarm relay contacts to outside circuitry alarm relay contacts to outside circuitry alarm relay contacts to outside circuitry The relay contacts are rated for 250 VAC 5 amps resistiv...

Page 7: ...gen using a span gas known quantity of oxygen per gas supplier or compressed air 20 9 oxygen In the single point method only one point in the calibration range is set using either span gas or compress...

Page 8: ...oxygen analyzer on a routine basis If the nitrogen purity level falls below the desired level readjust the flow control valve until the proper nitrogen purity level is reached Note If more than minor...

Page 9: ...vered from the system If the temperature difference is 10 F 20 F 5 C 11 C this equilibrium period may be as long as 60 minutes The inlet air tempera ture and more importantly inlet air dewpoint must n...

Page 10: ...vice schedule and replacement part numbers are outlined at the end of this section The calibra tion procedure for the oxygen analyzer is outlined on page 6 The analyzer should be calibrated on a regul...

Page 11: ...en servicing This equipment has fuses in both neutral and phase lines Use care when servicing Occasionally one or both of the fuses P N 13221 in the generator may burn out The fuses are located in the...

Page 12: ...ve 95 F 35 C the longevity of the membrane will be reduced and the warranty will be void 6 6 6 6 6 The drain lines from the first two stages of filtration should be piped away to an appropriate collec...

Page 13: ...58 F 50 C Particles 0 01 m None None Suspended Liquids None None Commercially Sterile Yes Yes Max Operating Pressure 145 psig 10 barg 145 psig 10 barg Maximum Pressure Drop 10 psi 0 7 bar 10 psi 0 7 b...

Page 14: ...d range during calibration Replace sensor P N 72695 Operating Conditions To arrange for system service contact the Technical Services Department at 1 800 343 4048 8AM to 5PM Eastern Time For location...

Page 15: ...cription Description Description Description Caution refer to accompanying documents for explanation Refer the caution warning note indicated for explantion Caution risk of electric shock 3 3 3 3 3 Ex...

Page 16: ...rhill MA 01835 0723 Tel 978 858 0505 Fax 978 556 7501 Parker Filtration Separation Parker Filtration Separation Parker Filtration Separation Parker Filtration Separation Parker Filtration Separation F...

Reviews: