Compax3 device description
High power devices
22
192-120149 N08 June 2014
3.4.2.
Connection of the power voltage
The terminal block of the drive can be found under the front cover. It is secured with
2 screws at the bottom of the device. Remove the bottom cover in order to access
the connection clamps.
Make sure that all live parts are covered by the housing after installation.
2
1
Illustration of the connection clamps exemplarily for all sizes:
L1, L2, L3: 3 phase mains connection
M1, M2, M3: Motor connections
DC+, DC-: DC link voltage
(1) DBR+ and DBR-: Connection of external braking resistor
(2) AUX1, AUX2: only with C3H1xxV4 external supply (AC) for device ventilator L, N
All
shields must be connected via a cable joint to the cable feed through plate.
Braking resistor and cable must be shielded if they are not installed in a control
cabinet.
The standard connection clamps of C3H090V4 and C3H1xxV4 are
not
suitable for
flat line bars.
Attention: The MOT/TEMP connection is not supported by the Compax3H050; do
therefore not wire this connection!
Terminal clamps - max. line cross sections
The line cross sections must correspond to the locally valid safety regulations. The
local regulations have always priority.
Power clamps
(minimum/maximum section)
C3H050V4
2.5 / 16mm
2
Massive
Multiwire
C3H090V4
16 / 50mm
2
25 / 50mm
2
C3H1xxV4
25 / 95mm
2
35 / 95mm
2
The standard connection clamps of Compax3H090V4 and Compax3H1xxV4 are
not suitable for flat line bars.
Cover plate for cable feed through
The cable feed through holes have the following dimensions:
C3H050V4
28.6mm for M20, PG16 and ½” NPT (America).
37.3mm for M32, PG29 and 1” NPT (America).
C3H090V4
22.8mm for M20, PG16 and ½” NPT (America).
28.6mm for M25, PG21 and ¾” NPT (America).
47.3mm for M40, PG36 and 1¼” NPT (America).
54.3mm for M50, PG42and 1½” NPT (America).
C3H1xxV4
22.8mm for M20, PG16 and ½” NPT (America)
28.6mm for M25, PG21 and ¾” NPT (America)