Section 3.0 – DRYER INSTALLATION
NEVER work on unit under pressure
NEVER work on unit when power is connected.
DO NOT over pressurize unit.
DO NOT pass air through the unit until it has been stabilized (operating 2 -
15 minutes). The larger the dryer, the longer it takes to stabilize. The
dryer is considered stabilized when the refrigeration suction gauge reads
between 28 to 35 PSI.
Plumbing the Air Lines
The dryers are shipped ready to run. All connections are made to the outside of
the cabinet.
Air piping must be supported independently of the dryer.
Direction of the air flow must be observed for proper
installation. (Fig. 1)
Use unions or flange joints on inlet and outlet pipe connections. (Fig. 2)
If vibration is present, flexible metal hoses must be installed to prevent the
vibration from being transmitted to the dryer.