background image

9

 

3.2 Connecting the generator

Refer to “Recommended system layout” on page 8 for the desired system configuration.

Apply eight turns of PTFE tape to the threads of the compression fittings supplied. Remove the labels covering the ports of the filters and insert 
the fittings. 

Connect the generator to the air supply through a pressure relief valve, pressure regulator and an isolation valve. Leave the valve in the 
closed position at this time. The pressure relief valve should be set at 11 bar g.

Fit a flow control valve, non-return valve and 3 way ball valve with silencer to the outlet filter of the generator. 

Connect the ball valve to the application using clean stainless steel or pre-cleaned refrigeration grade copper tubing and fittings. 
The tubing and fittings should be suitable for the application and rated to at least the maximum operating pressure of the generator.  

3.2.1 Electrical supply

Check the rating plate for the correct supply voltage and frequency. Select the required power cord and connect it to the switched IEC 320 
socket on the generator. Connect the plug directly to the electrical supply. Do not use an extension cord. 

3.2.2 Stacking the Generator

The generator may be re-configured so that the Parker Hannifin H and HMD range of hydrogen generators may be stacked safely on top of it. 
To re-configure the generator, unlock the two retaining screws and remove the top service lid panel (1). Remove the two retaining screws on the 
rear of the top lid panel (2). Slide the panel backwards until the nylon locating screws are free from their retaining slots and remove the panel. 

Remove the two screws holding the rear bracket in place. Lift the bracket away from the assembly and store it safely along with the top cover. 
Position the hydrogen generator on to the zero air generator. 

Note.

 The rubber feet on the hydrogen generator must be positioned in the locating holes (4) on the zero air generator chassis.

Ensure that the air supply and application piping are connected to the correct ports on the rear of the generator. Failure to 
observe the correct orientation could lead to excessive temperatures, burns, or fire.

Do not use plastic tubing to connect the generator to the application as this could cause contamination of the zero air.

Use PTFE on the BSPT fittings. Do not use sealing compounds as they could cause contamination of the zero air.

The upper plate is designed to withstand a maximum load of 30 kg (66lb). Do not place any objects other than the Parker Hannifin hydrogen 
generator on this plate.

Summary of Contents for domnick hunter UHP10ZA-S

Page 1: ...ro Air Generator UHP 10ZA S UHP 300ZA S Original Language User Guide aerospace climate control electromechanical filtration fluid gas handling hydraulics pneumatics process control sealing shielding E...

Page 2: ...ccordance with such instruction and with good practice The company shall not be under any liability whatsoever under the warranty if before giving notification in writing to the company as aforesaid t...

Page 3: ...layout 8 3 1 1 Installation Parts 8 3 2 Connecting the generator 9 3 2 1 Electrical supply 9 3 2 2 Stacking the Generator 9 4 Operating the equipment 10 4 1 Overview of the generator 10 4 2 Starting t...

Page 4: ......

Page 5: ...ed area and all of the vent ports on the rear of the generator are kept clear and free from blockages Use of the equipment in a manner not specified within this user guide may result in an unplanned r...

Page 6: ...be worn Gloves must be worn Warning Generator must be shut down and depressurised before performing any maintenance Refer to manual Caution Hot components enclosed Do not remove the cover until the u...

Page 7: ...cification is valid when the equipment is located installed operated and maintained as specified within this user guide Parameter Units UHP 10ZA S 35ZA S 50ZA S 75ZA S 150ZA S 200ZA S 300ZA S General...

Page 8: ...flicker in public low voltage supply systems for equipment with rated current 16 A per phase and not subject to conditional connection This equipment has been tested to and complies with the following...

Page 9: ...A S 325 12 8 340 13 4 425 16 7 219 8 6 10 2 22 5 35ZA S 455 17 9 340 13 4 425 16 7 330 13 0 14 2 31 3 50ZA S 455 17 9 340 13 4 425 16 7 330 13 0 14 2 31 3 75ZA S 455 17 9 340 13 4 425 16 7 330 13 0 14...

Page 10: ...s final location installation site and left to stabilise prior to unpacking Failure to do this could cause condensing humidity and potential failure of the generator 2 5 2 Unpacking Once ready to inst...

Page 11: ...llowed Class 1 Oil In each cubic metre of compressed air not more than 0 01 mg of oil is allowed Note This is the combined level for aerosol liquid and vapour ISO 8573 1 2010 Class 2 2 1 can be achiev...

Page 12: ...XPFA BP 1 8 OD Tube Non Return Valve 2A C2L 1 BN BP 1 4 OD Tube Non Return Valve 4A C4L 1 BN B 1 8 OD Tube Equal Tee 2ET2 B 1 4 OD Tube Equal Tee 4ET4 B 1 8 OD Tube Pressure Relief Valve This relief v...

Page 13: ...Generator The generator may be re configured so that the Parker Hannifin H and HMD range of hydrogen generators may be stacked safely on top of it To re configure the generator unlock the two retaini...

Page 14: ...or reaches the set temperature open the isolation valve located downstream of the generator Note The temperature may fluctuate up to 1 of the set temperature 6 The application instrument is now being...

Page 15: ...r leaks within the system Generator Check the mains supply cable for damage Generator Ensure there is ventilation clearance around generator Generator Replace the inlet and outlet filters Recommended...

Page 16: ...ck nut No 10 self tapping screw 120 V Fan Service Kit 606272526 606272526 Description Catalogue Number Technical Reference Contents 230 V Catalyst UHP 10ZA S 606272511 606272511 Catalyst assembly comp...

Page 17: ...Name Address Telephone Fax Contact Name Date of Commission Service Interval Months Hours Date Serviced By Comments Print Sign 6 4 000 12 8 000 18 12 000 24 16 000 30 20 000 36 24 000 42 28 000 48 32...

Page 18: ...sensor is open circuit Contact Parker Hannifin Indication Possible fault Condition Action Poor quality results downstream monitoring The generator is not powered Check the following 1 the generator i...

Page 19: ...supply cable is not damaged Contact Parker Hannifin Faulty controller or internal wiring fault Contact Parker Hannifin Indication Possible fault Condition Action Downstream monitoring Faulty cooling...

Page 20: ...r com NL The Netherlands Oldenzaal Tel 31 0 541 585 000 parker nl parker com NO Norway Asker Tel 47 66 75 34 00 parker norway parker com PL Poland Warsaw Tel 48 0 22 573 24 00 parker poland parker com...

Reviews: