background image

Parker Hannifin Corporation  

Industrial Gas Filtration and Generation Division  
Haverhill, MA 

•  1-800-343-4048

 

Parker Zero Air Generators 

 Models HPZA-3500, HPZA-7000, HPZA-18000, HPZA-30000

 

Bulletin TI-HPZA-3500H

 

 

     

 

 

Installation

 

 

General

 

 
 
 
 
 
 
 
 

 

 
Location

 

 

 

 

Utilities

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

All installation procedures for Parker Zero Air Generators should be performed by suitable 
personnel using reasonable care. See Figure 4 for Recommended Installation Schematic.

 

The Parker Zero Air Generator is a free-standing benchtop or wall mountable unit. When mounting the 
generator on the wall, use mounting hardware which is adequately sized to support the weight of the 
generator. The generator should be mounted to the wall (or similar mounting surface) in a vertical 
position according to National Electrical Code (NEC) and local building code guidelines. The mounting 
dimensions are shown in Figure 3.

 

A shut-off valve and a pressure regulator should be installed directly upstream from the Parker Zero Air 
Generator. The shut-off valve isolates the unit from the air line for maintenance and troubleshooting 
tasks. The pressure regulator controls the inlet air pressure and should be set to maintain a constant 
pressure between 40 psig and 125 psig (2.8 barg and 8.6 barg). Maintaining a constant inlet air 
pressure will minimize any system pressure fluctuations. Parker offers a pressure regulator, complete 
with a pressure gauge, as an accessory (P/N 72-130-V883). 

 
The Parker Zero Air Generator should be installed in an area relatively free from excessive dust and 
dirt, where the ambient temperature is between 60°F and 100°F (16°C and 43°C). 

Do not install the 

generator outdoors. 

There is no limit to the distance between the generator and the point of use as 

long as tubing type, size, cleanliness, and pressure drop are taken into consideration. Approximately 
6” of space should be allowed along the top and sides of the generator to ensure proper ventilation.

 

 

Compressed Air - 

The Parker Zero Air Generator requires a source of clean, dry compressed

 

air (40 psig-

125 psig/2.8 barg-8.6 barg) for optimal operation. The air should be as close to instrument quality as 
possible and supplied at a flow rate and pressure above those required at the point of use. The 
temperature and/or dewpoint of the supply air should be at room temperature (or lower), and the air 
should be relatively free of compressor oil, hydrocarbons, and particulate matter. Contamination of the 
catalyst bed may occur if it is exposed to certain compounds (warning below).  To prevent premature 
contamination of the catalyst module, the inlet to the compressed air supply compressor should be vented 
outdoors.

 

Chlorinated hydrocarbon compounds and chlorofluorocarbons (or freons) will permanently 
contaminate the hydrocarbon catalyst module in the Zero Air Generator.  Extreme care should 
be taken when specifying an air supply for the generator to ensure that these compounds are 
not present in the air supply nor likely to get into the compressor providing air to the 
generator.

 

The hydrocarbon catalyst module can also be contaminated by high concentrations of lead, 
sulfur, or phosphorous compounds, heavy metals, and long chain polymers. Care should be 
taken to avoid introducing these compounds into the Zero Air Generator. Specifically, assure 
that none of these compounds are stored near the inlet to the compressor supplying the 
system with compressed air. The intake for the compressor should be vented to the outdoors.

 

If the compressed air supply source is subject to halogenated hydrocarbon exposure, an auxiliary 
activated carbon scrubber (P/N 76080) should be installed directly upstream from the generator.

 

Connect the compressed air supply to the 

1/4” NPT (female) inlet port on the right side of the generator 

(see Figure 1). 

 
 
 
 
 
 
 
 
 
 

Summary of Contents for HPZA-3500

Page 1: ...e 1 are completely engineered systems which replace the use of inconvenient high pressure gas cylinders as a source of hydrocarbon free air The HPZA 30000 generators purify on site compressed air to a...

Page 2: ...rs are equipped with float drains which automatically open to empty any liquids from inside the filter housing The drains are connected to 1 4 O D plastic tubing which discharges to atmosphere onthe r...

Page 3: ...re taken into consideration Approximately 6 of space should be allowed along the top and sides of the generator to ensure proper ventilation Compressed Air The Parker Zero Air Generator requires a sou...

Page 4: ...ion only Piping Components The inlet and outlet ports for the Parker Zero Air Generator are 1 4 NPT female and located on right side of the unit Inlet tubing and fittings should be clean and rated for...

Page 5: ...stream from the generator Exposure of the generator to halogenated hydrocarbons will damage the catalyst module and void the warranty For additional information request the Analytical Gas Supplies cat...

Page 6: ...carbon content of less than 0 05 ppm Models HPZA 3500 HPZA 7000 and HPZA 18000 a flow control device must be installed downstream from the generator to prevent downstream demand in excess of the gener...

Page 7: ...Replace the GS membrane cartridge GS 050 05 95 and re assemble The time required to service all three stages of filtration integral to the Parker Zero Air Generator is approximately 15 minutes To prev...

Page 8: ...tor may burn out The fuses are located in the power receptacle on the left hand side of the generator Before servicing the fuses turn the generator off and disconnect the power cord from both the powe...

Page 9: ...generator is exceeded Overflow LED and yellow THC LEDs will illuminate An excessive pressure drop greater than 4 psig 0 3 bar may accompany an overflow situation If demand exceeds capacity install a f...

Page 10: ...arg 40 psig 125 psig 2 8 barg 8 6 barg 40 psig 125 psig 2 8 barg 8 6 barg Min Max ambient temperature 60 F 16 C 100 F 38 C 60 F 16 C 100 F 38 C 60 F 16 C 100 F 38 C 60 F 16 C 100 F 38 C Max relative h...

Page 11: ...calling for assistance WARRANTY NORTH AMERICA ONLY FOR INFORMATION CONTACT YOUR LOCAL REPRESENTATIVE Parker Hannifin guarantees to the original purchaser of this product that if the product fails or i...

Page 12: ...800 343 4048 Symbol Parker Hannifin Corporation Industrial Gas Filtration and Generation Division 242 Neck Road Haverhill MA 01835 www parker com labgas Description Caution Refer to accompanying docum...

Reviews: