On the ANI, there are multiple RS485 and RS232 ports. Ensure the connections
are made only to the communication ports specified below.
Figure 5: Active Network Interface (ANI) Terminals
4.4.3 RS 485 Connection
The RS485 cable from the junction box or dryer should be fed into the Remote
Communication Enclosure via an unused cable gland.
The cable should terminate in ANI terminal X02 and should be connected as
detailed in Table 1.
ANI Termination – X02
Dryer Plug Termination
X02 – 1 (L1)
L terminal (RS 485/ L1)
X02 – 2 (L2)
N terminal (RS 485/ L2)
X02 – 3 (Ground/ Earth)
E terminal (RS 485/ screen)
Table 1:ANI Cable Terminations – RS 485 Connection
4.4.4 RS232 Connection
The Remote Communications Enclosure is provided with a 5-metre RS232
communication cable already fitted. If required the RS232 cable can be
extended to a maximum of 20m
N.B.
Consideration should be given to network connections when
choosing a mounting position for the Remote Communications Enclosure.
The enclosure is rated to IP65/ NEMA 4 and should be placed in a
sheltered, indoor location.