2 Introduction
This manual is in reference to refrigeration dryers designed to remove water vapor from compressed
air.
2.1 Transportation
The packed unit must:
• remain upright;
• be protected against atmospheric agents;
• be protected against impacts.
2.2 Handling
Use a fork-lift truck suitable for the weight to be lifted, avoiding any type of impact.
2.3 Inspection
• All the units are assembled, wired, charged with refrigerant and oil and tested under standard
operating conditions in the factory;
• on receiving the machine check its condition: immediately notify the transport company in case of
any damage;
• unpack the unit as close as possible to the place of installation.
2.4 Storage
If several units have to stacked, follow the notes given on the packing. Keep the unit packed in a clean
place protected from damp and bad weather.
3 Installation
Y
Install indoors in a clean, dry area that is protected from the elements, direct sunlight and/or
other harsh conditions.
!
The product installed must be suitably protected against fi re risk (Ref. EN378-3).
3.1 Procedures
Y
Comply with the instructions given in par. 9.2 and 9.3.
All dryers must be fi tted with adequate pre-fi ltration near the dryer air inlet. Seller is excluded any
obligation of compensation or refund for any direct or indirect damage caused by its absence.
Y
Pre-fi lter element (for 3 micron fi ltration or better) must be replaced at least once a year, or
sooner as per manufacturer recommendations.
Y
Correctly connect the dryer to the compressed air inlet/outlet connections.
3.2 Operating space
Y
Leave a space of 1.5 m around the unit.
Leave a space of 2 m above dryer models with vertical condensation air expulsion.
3.3 Condenser version
Air-cooled version (Ac)
Do not create cooling air recirculation situations.
Do not obstruct the ventilation grilles.
Water-cooled version (Wc)
If not provided in the supply, fi t a mesh fi lter on the condensation water inlet.
Y,
Inlet condensation water characteristics:
Temperature
≥50°F (10°C)
CL
-
<50 ppm
ΔT
IN/OUT
5-15°C
CaCO
3
70-150 ppm
Max % glycol
50
O
2
<0.1 ppm
Pressure
43.5-145 PSIg (3-10 barg)
Fe
<0.2 ppm
PH
7.5-9
NO
3
<2 ppm
Electrical conductivity
10-500 μS/cm
HCO
3
-
70-300 ppm
Langelier saturation index
0-1
H
2
S
<0.05 ppm
SO
4
2-
<50 ppm
CO
2
<5 ppm
NH
3
<1 ppm
Al
<0.2 ppm
Please note that for special cooling water types such as demineralized, deionized or distilled it is
necessary to contact the manufacturer to verify which kind of condenser should be used since the
standard material may not be suitable.
3.4 Tips
To prevent damage to the internal parts of the dryer and air compressor, avoid installations where
the surrounding air contains solid and/or gaseous pollutants (e.g. sulphur, ammonia, chlorine and
installations in marine environments).
The ducting of extracted air is to be avoided for versions with axial fans.
3.5 Electrical connection
Use approved cable in conformity with the local laws and regulations (for minimum cable section, see
par. 9.3).
Install a differential thermal magnetic circuit breaker with contact opening distance 3 mm ahead of
the system (RCCB - IDn = 0.3A) (see the relevant current local regulations).
The nominal current In of the magnetic circuit breaker must be equal to the FLA with an intervention
curve type D.
Select the power supply and insert a bridge as shown below:
S7-S6 for 400/3/50
S8-S6 for 460/3/60
Inside the electrical panel there is an instruction label.
3.6 Condensate drain connection
Summary of Contents for PSE 325
Page 2: ......
Page 76: ...14 PSE 325 1000 60Hz 9 7 REFRIGERANT CIRCUIT PSE325 500 Ac PSE325 500 ...
Page 77: ...15 PSE 325 1000 60Hz REFRIGERANT CIRCUIT PSE700 1000 Ac PSE700 PSE800 PSE1000 ...
Page 78: ...16 PSE 325 1000 60Hz REFRIGERANT CIRCUIT PSE700 1000 Wc PSE700 PSE800 PSE1000 ...
Page 87: ...25 PSE 325 1000 60Hz WIRING DIAGRAM PSE700 1000 Sheet 1 of 10 ...
Page 89: ...27 PSE 325 1000 60Hz WIRING DIAGRAM PSE700 1000 Sheet 3 of 10 700 800 1000 ...
Page 90: ...28 PSE 325 1000 60Hz WIRING DIAGRAM PSE700 1000 Sheet 4 of 10 ...
Page 91: ...29 PSE 325 1000 60Hz WIRING DIAGRAM PSE700 1000 Sheet 5 of 10 ...
Page 92: ...30 PSE 325 1000 60Hz WIRING DIAGRAM PSE700 1000 Sheet 6 of 10 ...
Page 93: ...31 PSE 325 1000 60Hz WIRING DIAGRAM PSE700 1000 Sheet 7 of 10 ...
Page 94: ...32 PSE 325 1000 60Hz WIRING DIAGRAM PSE700 1000 Sheet 8 of 10 ...
Page 95: ...33 PSE 325 1000 60Hz WIRING DIAGRAM PSE700 1000 Sheet 9 of 10 ...
Page 96: ...34 PSE 325 1000 60Hz WIRING DIAGRAM PSE700 1000 Sheet 10 of 10 700 1000 ...
Page 97: ......
Page 98: ......
Page 99: ......