background image

isysNet Relay Output Module, Series A (PSSTR4M12A) 

E109P

8

Relay Output Modules

Outputs per Module 

4 Form A isolated (normally open) electromechanical relays

Output Voltage Range (load dependent) 

5-28.8VDC @ 2.0A resistive

Output Current Rating (at rated power) 

Resistive:

  2A @ 5-28.8VDC 

 

Inductive:

  2.0A steady state @ 5-28.8VDC, L/R = 7 ms

Output Signal Delay OFF to ON, Maximum

1

 

10 ms (time from valid output on signal to relay energization by module)

Output Delay Time, ON to OFF, Maximum

1

 

26 ms (time from valid output off signal to relay deenergization by module)

Off-State Leakage Current (Max. at 240VAC) 

1.2 mA and bleed resistor through snubber circuit

Power Rating (steady state) 

60W max. for 28.8VDC resistive output 

 

60VA max. for 28.8VDC inductive output

Initial Contact Resistance 

30 mW

Switching Frequency, Maximum 

1 operation/3s (0.3 Hz at rated load)

Operate/Release Time, Maximum 

10 ms

Bounce Time 

1.2 ms (mean)

Minimum Contact Load 

100µA at 100 mVDC

Expected Life of Electrical Contacts 

Minimum 100,000 operations @ rated loads

Fusing 

Module outputs are not fused.  If fusing is desired, you must supply external fusing.

Keyswitch Position 

7

LED Indicators 

4 yellow output status, logic side 

 

1 green/red network status, logic side 

 

1 green/red module status, logic side

PointBus Current, Maximum 

90 mA @ 5VDC

Power Dissipation, Maximum 

0.5W @ 28.8VDC 

Thermal Dissipation, Maximum 

1.7 BTU/hr. @ 28.8VDC

Isolation Voltage 

 

Between any 2 sets of contacts 

Tested to withstand 2550VDC for 60s 

Customer load to logic 

Tested to withstand 2550VDC for 60s

Field Power Bus 

  Supply Voltage 

None required 

  Voltage Range, Maximum 

5-28.8VDC 

  Supply Current 

2A per channel maximum, 8A per module

Dimensions 

Inches (Metric)  1.25H x 2.63W x 4.25D (31.75H x 66.80W x 107.95D)

Operating Temperature 

IEC 60068-2-1 (Test Ad, Operating Cold), 

 

IEC 60068-2-2 (Test Bd, Operating Dry Heat), 

 

IEC 60068-2-14 (Test Nb, Operating Thermal Shock): 

 

-20 to 60°C (-4 to 140°F)

Storage Temperature 

IEC 60068-2-1 (Test Ab, Un-packaged Non-operating Cold), 

 

IEC 60068-2-2 (Test Bb, Un-packaged Non-operating Dry Heat), 

 

-40 to 85°C (-40 to 185°F)

Relative Humidity 

IEC 60068-2-30 (Test Db, Un-packaged Non-operating Damp Heat):  5 to 95% non-condensing

Shock 

IEC60068-2-27 (Test Ea, Unpackaged Shock): 

 

Operating 15g, Non-operating 50g

Vibration 

IEC60068-2-6 (Test Fc, Operating):  2g @ 10 to 500Hz

ESD Immunity 

IEC 61000-4-2: 

 

6kV contact discharges, 8kV air discharges

Radiated RF Immunity 

IEC 61000-4-3: 

 

10V/m with 1kHz sine-wave 80%AM from 80MHz to 2000MHz 

 

10V/m with 200Hz 50% Pulse 100%AM at 900Mhz 

 

10V/m with 200Hz 50% Pulse 100%AM at 1890Mhz

EFT/B Immunity 

IEC 61000-4-4:  ±3kV at 5kHz on signal ports

Surge Transient Immunity 

IEC 61000-4-5:  ±1kV line-line(DM) and ±2kV line-earth(CM) on signal ports

Conducted RF Immunity 

IEC 61000-4-6:  10Vrms with 1kHz sine-wave 80%AM from 150kHz to 80MHz

Emissions 

CSPR 11:  Group 1, Class A

Enclosure Type Rating 

Meets IP65/66/67 (when marked)

Mounting Base Screw Torque 

#8 screw, 7.5 in. lbs. in Aluminum, 16 in. lbs. in Steel

Wiring Category

2

 

1 - on signal ports

Weight 

Imperial (Metric)  0.637 lb. (0.289 kg)

Certifications: 

c-UL-us  UL Listed Industrial Control Equipment, 

(when product is marked) 

 

certified for US and Canada

 

CE

 

European Union 89/336/EEC EMC Directive, 

 

 

compliant with: 

 

 

EN 61000-6-4; Industrial Emissions 

 

 

EN 50082-2; Industrial Immunity 

 

 

EN 61326; Meas./Control/Lab., Industrial Requirements 

 

 

EN 61000-6-2; Industrial Immunity 

 

 

European Union 73/23/EEC LVD Directive, compliant with: 

 

 

EN61131-2; Programmable Controllers

 

C- Tick  Australian Radiocommunications Act, compliant with: 

 

 

AS/NZS CISPR 11; Industrial Emissions

  1. OFF to ON or ON to OFF delay is time from a valid output “on” or “off” signal to output energization or de-energization.
  2. Use this Conductor Category information for planning conductor routing. Refer to Publication E115P, “Industrial Automation Wiring and Grounding Guidelines”.

Specifications

 - 

Following are specifications for the PSSTR4M12A relay output module.

Summary of Contents for PSSTR4M12A

Page 1: ...hat all performance safety and warning requirements of the application are met The products described herein including without limitation product features specifications designs availability and prici...

Page 2: ...s Attentions help you Identify a Hazard Avoid a Hazard Recognize the Consequence SHOCK HAZARD Labels may be located on or inside the equipment to alert people that dangerous voltage may be present BUR...

Page 3: ...and Tap for M6 Screw Ground Lug Connection Latching Mechanism Mounting Base Keyswitch Set to position 7 for the PSSTR4M12A relay output modules Install the Mounting Base as Follows 1 Lay out the requ...

Page 4: ...odule down until it engages the latching mechanism You will hear a clicking sound when the module is properly engaged The locking mechanism will lock the module to the base Remove the Relay Output Mod...

Page 5: ...ur Module I O messages are sent to consumed and received from produced the I O module These messages are mapped into the processor s memory The I O relay output module consumes 1 byte of output data s...

Page 6: ...e that the PSSTR4M12A is now under the I O configuration Add Relay Output Module to RSLogix 5000 I O Configuration To add your relay output module to RSLogix 5000 I O configuration follow these steps...

Page 7: ...cation faulted device the device has detected a network access error and is in communication faulted state Device has received and accepted an Identity Communication Faulted Request long protocol mess...

Page 8: ...Test Nb Operating Thermal Shock 20 to 60 C 4 to 140 F Storage Temperature IEC 60068 2 1 Test Ab Un packaged Non operating Cold IEC 60068 2 2 Test Bb Un packaged Non operating Dry Heat 40 to 85 C 40 to...

Reviews: