Parker Hannifin S.p.A S.B.C. Division
SLVDN User’s Manual
Page 175 of 181
15.Appendix B: Software timing
Periodo Task
64
μ
s
speed control
128
μ
s
controllo di velocità
128
μ
s
Speed reference management
512
μ
s
Fast operating modes management
512
μ
s
Torque limits management
512
μ
s
Braking resistor management
512
μ
s
FIN management
2,048 ms
Operating modes management
6,144 ms
Thermal motor image
6,144 ms
Digital inputs
6,144 ms
Program scanning pico-PLC
6,144 ms
Digital outputs
49,152 ms
Speed window management
16.Appendix C: Default program for the pico-PLC
90.0
40.6
END
41.5
90.1
91.0
41.4
91.1
41.11
LD
90.0
OUT 41.5
LD 90.1
OUT 40.6
LD 41.4
OUT 91.0
LD 41.11
OUT 91.1
END
digital input 0 used to power
the drive
digital input 1 used for the stop
function
digital output 0 indicates that
the converter is OK
digital output 1 indicates that
the thermal motor image is
active
end of the program