5.5. Line connection diagrams
The SLVD-N converter can be connected to the power supply in various ways.
If a transformer with an electrostatic shield between the primary and the secondary is used,
EMC filters will not have to be installed. If an auto-transformer, a transformer without
electrostatic shield or a direct connection to the power network is used, EMC filters must be
used.
The converter can be used only in grounded TT and TN industrial networks with a max. short
circuit symmetrical current of 5kA maximum at 230V +10%.
Do not use in ungrounded networks or in networks with asymmetrical grounding (IT)
Use of a transformer connected the secondary in a star configuration with electrostatic
shield
(10, 15 and 17 versions have two PE pins)
Use of the auto-transformer
(10, 15 and 17 versions have two PE pins)