Parker Hannifin S.p.A S.B.C. Division
SLVDN User’s Manual
Page 51 of 181
8.2. “High” voltage power supply
In “high ” voltage operating mode (b40.10=0), the converter can supplied as follows:
-
AC 3-phase network ((200÷230 ±10%) and AC 1-phase network (200÷230
±10%)
Set b39.0=0 (default).
The converter can automatically detect the power supply voltage rating and
adapts internal operating parameters accordingly..
-
Continuous (14÷325 ±10%)
Set b39.0=1 and set the nominal value of continuous voltage in Pr206. Save,
switch off and on again the converter.
The automatic reset of “under voltage” undervoltage alarm can be forced by b99.8=1 with any
kind of power supply (it’s necessary save the parameters to enable the command at the
successive start up of the drive).